Kenmore 8804 Installation Instructions - Page 4

Supply, Requirements - parts

Page 4 highlights

Do not allow combustible materials (for example: clothing, draperies/curtains, paper) to come in contact with exhaust system. The dryer MUST NOT be exhausted into a chimney, a wall, a ceiling, or any concealed space of a building which can accumulate lint, resulting in a fire hazard. Exceeding the length of duct pipe or number of elbows allowed in the "MAXIMUM LENGTH" charts can cause an accumulation of lint in the exhaust system. Plugging the system could create a fire hazard, as well as increase drying times. Do not screen the exhaust ends of the vent system, nor use any screws or rivets to assemble the exhaust system. Lint can become caught in the screen, on the screws or rivets, clogging the duct work and creating a fire hazard as well as increasing drying times. Use an approved vent hood to terminate the duct outdoors, and seal all joints with duct tape. All male duct pipe fittings MUSTbe installed downstream with the flow of air. Explosion hazard. Do not install the dryer where gasoline or other flammables are kept or stored. If the dryer is installed in a garage, it must be a minimum of 18 inches (45.7 cm) above the floor. Failure to do so can result in death, explosion, fire or burns. Number of 90 ° Turns MAXIMUM LENGTH of 4" 110.2 cm) Dia. Rigid Metal VENT HOOD TYPE (Preferred) Duct Louvered 0 1 2 3 4 Number of 90 ° Turns (10.2 cm) 60 ft.(18.28 m) 52ft.(IS.84m) 44 ft.113.41 m) 32 ft.(9.zsm) 2 _/2'_. (6.35 cm) 48 ft.114.63 m) 40 ft.(12.19 In) 32ft. 19.75m) 24ft. {7.31m) 28 ft.(8.53 m) MAXIMUM 16ft. (4.87m) LENGTH of 4" (10.2 cm) Dia. Flexible Metal Duct VENT HOOD TYPE (Preferred) I. Connect an inclined or digital manometer between the dryer and the point the exhaust connects to the dryer. 2. Set the dryer timer and temperature to air fluff (cool down) and start the dryer. 3. Read the measurement on the manometer. 4. The system back pressure MUSTNOT be higher than 0.75 inches of water column. If the system back pressure is lessthan 0.75 inches of water column, the system is acceptable. If the manometer reading is higher than 0.75 inches of water column, the system is too restrictive and the installation is unacceptable. Although vertical orientation of the exhaust system is acceptable, certain extenuating circumstances could affect the performance of the dryer: • Only the rigid metal duct work should be used. • Venting vertical through a roof may expose the exhaust system to down drafts causing an increase in vent restriction. • Running the exhaust system through an uninsulated area may cause condensation and faster accumulation of lint. • Compression or crimping of the exhaust system will cause an increase in vent restriction. The exhaust system should be inspected and cleaned a minimum of every 18months with normal usage. The more the dryer is used, the more often you should check the exhaust system and vent hood for proper operation. EXHAUST DIRECTION All dryers shipped from the factory are set up for rear exhausting. However, on electric dryers, exhausting can be to the right or left side of the cabinet or the bottom of the dryer. On gas dryers, exhausting can be to the right side of the cabinet or the bottom of the dryer. Directional exhausting can be accomplished by installing Exhaust Kit, P/N 131456800, available through your parts distributor. Follow the instructions supplied with the kit. EXHAUST DUCT LOCATING DIMENSIONS I/ I _'}_ k. SAME AS OTHER SIDE ./" 5 718" /_,31=j (10.2 cm) 0 3Oft. (9.14 m) (6.35 cm) 18 ft. (5.49 m) GAS SUPPLY REQUIREMENTS 1 22 ft. (6.71 m} 14 ft. (4.27 m) Replace copper connecting pipe that is not 2 14 ft. (4.27 m) 10 ft. (3.05 m) plastic-coated. Stainless steel or plastic-coated brass MUST 3 NOT RECOMMENDED be used. I. Installation MUSTconform with local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (latest edition). 2. The gas supply line should be of 1/2 inch (1.27 cm) pipe. INSTALML ALEFITTINGISN CORRECDTIRECTION 3. If codes allow, flexible metal tubing may be used to connect your dryer to the gas supply line. The tubing MUST be In installations where the exhaust system is not described in the constructed of stainless steel or plastic-coated brass. charts, the following method must be used to determine if the 4. The gas supply line MUSThave an individual shutoff valve. exhaust system is acceptable: 4

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

Do
not
allow
combustible
materials
(for
example:
clothing,
draperies/curtains,
paper)
to come
in
contact
with
exhaust
system.
The dryer
MUST
NOT
be
exhausted into a chimney, a wall, a ceiling, or any concealed
space of a building which can accumulate lint, resulting in a fire
hazard.
Exceeding
the length
of
duct
pipe
or
number
of
elbows
allowed
in the
"MAXIMUM
LENGTH" charts
can
cause an accumulation
of lint in the exhaust system.
Plugging
the system could create a fire hazard, as well as increase drying
times.
Do not screen the exhaust
ends of the vent
system,
nor
use any screws
or
rivets
to
assemble
the
exhaust
system.
Lint can become caught in the screen, on the
screws or rivets, clogging the duct work and creating a fire hazard
as well as increasing drying times. Use an approved vent hood
to terminate the duct outdoors, and seal all joints with duct tape.
All male duct pipe fittings
MUSTbe
installed downstream
with
the flow of air.
Explosion
hazard.
Do not install
the dryer
where
gasoline
or other
flammables
are kept
or stored.
If
the dryer is installed in a garage, it must be a minimum
of 18
inches (45.7 cm) above the floor. Failure to do so can result in
death, explosion, fire or burns.
Number
of
90
°
Turns
0
1
2
3
4
Number
of
90
°
Turns
0
1
2
3
MAXIMUM
LENGTH
of
4" 110.2 cm)
Dia. Rigid
Metal
Duct
VENT HOOD
TYPE
(Preferred)
Louvered
(10.2
cm)
60
ft.(18.28
m)
52
ft.(IS.84m)
44 ft.113.41
m)
32
ft.(9.zsm)
28 ft.(8.53
m)
MAXIMUM
LENGTH
of 4"
(10.2
cm)
Dia.
Flexible
Metal
Duct
VENT HOOD
TYPE
(Preferred)
(10.2
cm)
3Oft.
(9.14
m)
22 ft.
(6.71
m}
14
ft.
(4.27 m)
NOT RECOMMENDED
2
_/2'_.
(6.35
cm)
48
ft.114.63
m)
40
ft.(12.19
In)
32ft.
19.75m)
24ft.
{7.31m)
16ft.
(4.87m)
(6.35 cm)
18
ft.
(5.49 m)
14
ft.
(4.27 m)
10
ft.
(3.05 m)
INSTALL
MALEFITTINGS
INCORRECT
DIRECTION
In installations where the exhaust system is not described in the
charts, the following
method must be used to determine
if the
exhaust system is acceptable:
I.
Connect
an inclined or digital manometer between the
dryer and the point the exhaust connects to the dryer.
2.
Set the dryer timer and temperature to air fluff (cool
down) and start the dryer.
3.
Read the measurement on the manometer.
4.
The system back pressure
MUSTNOT
be higher than
0.75 inches of water column.
If the system back
pressure is lessthan 0.75 inches of water column, the
system is acceptable.
If the manometer reading is
higher than 0.75 inches of water column, the system is
too restrictive and the installation is unacceptable.
Although vertical orientation
of the exhaust system is
acceptable, certain extenuating
circumstances could affect the
performance of the dryer:
Only the rigid metal duct work should be used.
Venting vertical through a roof may expose the exhaust
system to down drafts causing an increase in vent
restriction.
Running the exhaust system through an uninsulated
area may cause condensation and faster accumulation
of lint.
Compression or crimping of the exhaust system will
cause an increase in vent restriction.
The exhaust system should be inspected and cleaned a
minimum of
every
18months
with normal usage. The more the
dryer is used, the more often you should check the exhaust
system and vent hood for proper operation.
EXHAUST DIRECTION
All dryers shipped from the factory are set up for rear exhausting.
However, on electric dryers, exhausting can be to the right or left
side of the cabinet or the bottom
of the dryer. On gas dryers,
exhausting can be to the right side of the cabinet or the bottom of
the dryer. Directional exhausting can be accomplished by installing
Exhaust Kit,
P/N 131456800,
available
through
your
parts
distributor. Follow the instructions supplied with the kit.
EXHAUST DUCT LOCATING DIMENSIONS
I
/
SAME AS OTHER SIDE
I
_'}_
./"
5 718"
k.
/_,31=
j
GAS
SUPPLY
REQUIREMENTS
Replace copper
connecting
pipe that
is not
plastic-coated.
Stainless steel or plastic-coated
brass MUST
be used.
I.
Installation
MUSTconform
with local codes, or in the absence
of local codes, with the National Fuel Gas Code, ANSI Z223.1
(latest edition).
2. The gas supply line should be of 1/2 inch (1.27 cm) pipe.
3.
If codes allow, flexible metal tubing
may be used to connect
your
dryer
to
the gas supply
line. The tubing
MUST
be
constructed of stainless steel or plastic-coated brass.
4. The gas supply line
MUSThave
an individual shutoff
valve.
4