LG ARUN038GS2 Installation Manual - Page 32
Outdoor Unit
View all LG ARUN038GS2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 32 highlights
Prohibited pattern HR1 1 2 3 4 48k 48k 48k 48k • Capacity sum of indoor units is over 160kBtu/hr. Pattern Pattern A HR1 HR2 1 2 3 4 36k 36k 36k 36k A HR1 HR2 1234 12k 24k 24k 12k 5678 48k 48k 48k 12k 1 Indoor unit A Y Branch pipe Outdoor Unit Low pressure Gas pipe High pressure Gas pipe Liquid pipe HR Unit Gas pipe Liquid pipe Indoor Unit 1) Keep the 40m distance from the first branch to the farthest indoor. 2) Keep the horizontal level between HR units.( for example, the same flour. ) 1) under 40m 2) Same horizontal level It's not allowed Height Y branch Indoor Unit Indoor Unit Indoor Unit Indoor Unit Keep the sum of indoor capacity is under 160kBtu/hr 1) under 40m 2) Same horizontal level Indoor Indoor Indoor Indoor Unit Unit Unit Unit Indoor Indoor Indoor Indoor Unit Unit Unit Unit Keep the sum of indoor capacity is under 160kBtu/hr 32 Outdoor Unit