LG ARUN038GS2 Installation Manual - Page 42
Caution
View all LG ARUN038GS2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 42 highlights
Electrical Wiring Outdoor Unit Outdoor Unit Indoor Unit Indoor Unit Remote controller Remote controller Outdoor Unit Indoor Unit Indoor Unit Remote controller Remote controller 2-Core Shield Cable Indoor Unit Indoor Unit Remote controller Remote controller Outdoor Unit Indoor Unit Indoor Unit Remote controller Remote controller Multi-Core Cable Outdoor units Master Slave1 Slave2 Indoor unit Indoor unit HR unit Remote Remote controller controller Outdoor units Master Slave1 Slave2 Indoor unit Indoor unit HR unit Remote Remote controller controller 2-core shield cable Outdoor units Master Slave1 Slave2 Outdoor units Master Slave1 Slave2 Indoor unit Indoor unit HR unit Remote controller Remote controller Indoor HR unit unit Indoor unit Remote controller Remote controller Multi-core cable CAUTION • Use the 2-core shield cables for communication lines. Never use them together with power cables. • The conductive shielding layer of cable should be grounded to the metal part of both units. • Never use multi-core cable • As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating. Therefore, never install a phase leading capacitor. • Keep power imbalance within 2% of the supply rating. Large imbalance will shorten the life of the smoothing capacitor. 42 Outdoor Unit