LG ARUN038GS2 Installation Manual - Page 83
Display, Title, Cause of Error, Outdoor unit related error
View all LG ARUN038GS2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 83 highlights
ENGLISH Outdoor unit related error Test Run Display Title Cause of Error 1 Master Outdoor Unit High Pressure Switch System is turned off by Master Outdoor Unit high pressure switch. 2 4 2 Slave1 Outdoor Unit High Pressure Switch System is turned off by slave1 Outdoor Unit high pressure switch. 3 Slave2 Outdoor Unit High Pressure Switch System is turned off by slave2 Outdoor Unit high pressure switch. Master Outdoor Unit Input Voltage High/ 1 Low Voltage Master Outdoor Unit input voltage is over 487V or below 270V Slave1 Outdoor Unit Input Voltage High/ 2 5 2 Low Voltage Slave1 Outdoor Unit input voltage is over 487V or below 270V Slave2 Outdoor Unit Input Voltage High/ 3 Low Voltage Slave2 Outdoor Unit input voltage is over 487V or below 270V Master Outdoor Unit Inverter Compressor 1 Start Failure The First Start Failure by Master Outdoor Unit Inverter Compressor Abnormality 2 6 Slave1 Outdoor Unit Inverter Compressor 2 Start Failure The First Start Failure by Slave1 Outdoor Unit Inverter Compressor Abnormality Slave2 Outdoor Unit Inverter Compressor 3 Start Failure The First Start Failure by Slave2 Outdoor Unit Inverter Compressor Abnormality Master Outdoor Unit Inverter DC link High 1 Voltage System is turned off by Master Outdoor Unit DC Voltage Over Charging 2 8 Slave1 Outdoor Unit Inverter DC link High 2 Voltage System is turned off by Slave1 Outdoor Unit DC Voltage Over Charging Slave2 Outdoor Unit Inverter DC link High 3 Voltage System is turned off by Slave2 Outdoor Unit DC Voltage Over Charging Master Outdoor Unit Inverter Compressor 1 Over Current Master Outdoor Unit Inverter Compressor Fault OR Drive Fault 2 9 Slave1 Outdoor Unit Inverter Compressor 2 Over Current Slave1 Outdoor Unit Inverter Compressor Fault OR Drive Fault Slave2 Outdoor Unit Inverter Compressor 3 Over Current Slave2 Outdoor Unit Inverter Compressor Fault OR Drive Fault Master Outdoor Unit Inverter Compressor 1 High Discharge Temperature System is turned off by Master Outdoor Unit Inverter Compressor High Discharge Temperature 3 2 Slave1 Outdoor Unit Inverter Compressor 2 High Discharge Temperature System is turned off by Slave1 Outdoor Unit Inverter Compressor High Discharge Temperature Slave2 Outdoor Unit Inverter Compressor 3 Discharge High Temperature System is turned off by Slave2 Outdoor Unit Inverter Compressor High Discharge Temperature Master Outdoor Unit Constant Speed 1 Compressor High Discharge Temperature System is turned off by Master Outdoor Uunit Constant Speed High Discharge Temperature 3 3 Slave1 Outdoor Unit Constant Speed 2 Compressor High Discharge Temperature System is turned off by Slave1 Outdoor Unit Constant Speed High Discharge Temperature Slave2 Outdoor Unit Constant Speed 3 Compressor High Discharge Temperature System is turned off by Slave2 Outdoor Unit Constant Speed High Discharge Temperature High Pressure of Master Outdoor Unit 1 System is turned off by excessive increase of high pressure of Master Outdoor Unit High Pressure of Slave1 Outdoor Unit 342 System is turned off by excessive increase of high pressure of Slave1 Outdoor Unit High Pressure of Slave2 Outdoor Unit 3 System is turned off by excessive increase of high pressure of Slave2 Outdoor Unit Low Pressure of Master Outdoor Unit 1 System is turned off by excessive decrease of low pressure of Master Outdoor Unit Low Pressure of Slave1 Outdoor Unit 352 System is turned off by excessive decrease of low pressure of Slave1 Outdoor Unit Low Pressure of Slave2 Outdoor Unit 3 System is turned off by excessive decrease of low pressure of Slave2 Outdoor Unit Installation Manual 83