LG CBGS3628S INSTALLATION - Page 10

Electrical Connections

Page 10 highlights

en-us_main.book.book Page 10 Friday, November 4, 2022 8:08 AM 10 INSTALLATION for leaks. Tighten all connections, if necessary, to prevent gas leakage in the cooktop or supply line. WARNING • DO NOT USE A FLAME TO CHECK FOR GAS LEAKS. • The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). • The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa). Flexible Connector Hookup NOTE • Installer: Inform the consumer of the location of the gas shut-off valve. 3. Electrical Connections Electrical Requirements This cooktop requires a 120 Volt, 60 Hertz, properly grounded dedicated circuit protected by a 15 A or 20 A circuit breaker or time-delay fuse. The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, NFPA70 or the Canadian Electric Code, CSA C22.1-02. Grounding IMPORTANT: FOR PERSONAL SAFETY, THIS APPLIANCE MUST BE PROPERLY GROUNDED. Preferred Method a Pressure Regulator b Adapter c Gas Flow into Range d Flex Connector (3 ft. max. in US, 6 ft. max. in Canada) e Adapter f Gas Shut-off Valve g 1/2" or 3/4" Gas Pipe a Ensure proper ground exists before use. The power cord of this appliance should be equipped with a three-prong (grounding) plug which mates with a standard three-prong grounding wall receptacle to reduce the possibility of electric shock hazard from this appliance. The customer should have the wall receptacle and circuit checked by a qualified technician to be sure the receptacle is properly grounded. When connecting this cooktop, it is the personal responsibility and obligation of the customer to have a standard two-prong wall receptacle replaced with a properly grounded three-prong wall receptacle. DO NOT, UNDER ANY CIRCUMSTANCES, CUT OR REMOVE THE THIRD (GROUND) PRONG FROM THE POWER CORD. A word about Ground Fault Circuit Interrupters - A Ground Fault Circuit Interrupter (GFCI) is not required or recommended for gas range receptacles.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44

10
INSTALLATION
for leaks. Tighten all connections, if necessary,
to prevent gas leakage in the cooktop or
supply line.
WARNING
DO NOT USE A FLAME TO CHECK FOR GAS LEAKS.
The appliance and its individual shutoff valve
must be disconnected from the gas supply
piping system during any pressure testing of
that system at test pressures in excess of 1/2 psi
(3.5 kPa).
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shutoff valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa).
Flexible Connector Hookup
a
Pressure Regulator
b
Adapter
c
Gas Flow into Range
d
Flex Connector (3 ft. max. in US, 6 ft. max. in
Canada)
e
Adapter
f
Gas Shut-off Valve
g
1/2” or 3/4” Gas Pipe
NOTE
Installer: Inform the consumer of the location of
the gas shut-off valve.
3. Electrical Connections
Electrical Requirements
This cooktop requires a 120 Volt, 60 Hertz,
properly grounded dedicated circuit protected by
a 15 A or 20 A circuit breaker or time-delay fuse.
The appliance, when installed, must be electrically
grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical
Code, NFPA70 or the Canadian Electric Code, CSA
C22.1-02.
Grounding
IMPORTANT: FOR PERSONAL SAFETY, THIS
APPLIANCE MUST BE PROPERLY GROUNDED.
Preferred Method
a
Ensure proper ground exists before use.
The power cord of this appliance should be
equipped with a three-prong (grounding) plug
which mates with a standard three-prong
grounding wall receptacle to reduce the possibility
of electric shock hazard from this appliance.
The customer should have the wall receptacle and
circuit checked by a qualified technician to be sure
the receptacle is properly grounded.
When connecting this cooktop, it is the personal
responsibility and obligation of the customer to
have a standard two-prong wall receptacle
replaced with a properly grounded three-prong
wall receptacle.
DO NOT, UNDER ANY CIRCUMSTANCES, CUT OR
REMOVE THE THIRD (GROUND) PRONG FROM THE
POWER CORD.
A word about Ground Fault Circuit Interrupters – A
Ground Fault Circuit Interrupter (GFCI) is not
required or recommended for gas range
receptacles.
en-us_main.book.book
Page 10
Friday, November 4, 2022
8:08 AM