LiftMaster MGJ MGJ S-SERIES Manual - Page 7

Entrapment Protection Accessories (optional), Limit Switch Adjustment

Page 7 highlights

ENTRAPMENT PROTECTION ACCESSORIES (OPTIONAL) ELECTRIC SENSING EDGES Electric sensing edges with an isolated normally open (N.O.) output are compatible with your operator. If your door does not have a bottom sensing edge and you wish to purchase one, contact the supplier of your operator. IT IS STRONGLY RECOMMENDED THAT A SENSING EDGE OR OTHER ENTRAPMENT PROTECTION DEVICE BE USED IN CONJUNCTION WITH THIS OPERATOR. If not pre-installed by the door manufacturer, mount the sensing edge on the door according to the instructions provided with the edge. The sensing edge may be electrically connected by either coiled cord or take-up reel. Refer to the steps below Important Notes: a) Proceed with Limit Switch Adjustments before making any sensing edge wiring connections to operator as described below. b) Electrician must hardwire the junction box to the operator electrical box in accordance with local codes. WARNING W AN ELECTRIC SENSING EDGE IS REQUIRED WHEN USING THIS OPERATOR IN CONJUNCTION WITH THE SS90 FIRE DOOR CONTROLLER. TAKE-UP REEL: Take-up reel should be installed 12" above the top of the door. CAUTION COIL CORD: Connect operator end of coil cord to junction box (not supplied) fastened to the wall approximately halfway up the door opening. LIMIT SWITCH ADJUSTMENT MAKE SURE THE LIMIT NUTS ARE POSITIONED BETWEEN THE LIMIT SWITCH ACTUATORS BEFORE PROCEEDING WITH ADJUSTMENTS. 1. To adjust limit nuts depress retaining plate to allow nut to spin freely. After adjustment, release plate and ensure it seats fully in slots of both nuts. 2. To increase door travel, spin nut away from actuator. To decrease door travel, spin limit nut toward actuator. 3. Adjust open limit nut so that door will stop in open position with the bottom of the door even with top of door opening. 4. Repeat Steps 1 and 2 for close cycle. Adjust close limit nut so that actuator is engaged as door fully seats at the floor. CLOSE Limit Switch WARNING TO AVOID SERIOUS PERSONAL INJURY OR DEATH FROM ELECTROCUTION, DISCONNECT ELECTRIC POWER BEFORE MANUALLY MOVING LIMIT NUTS. CAUTION OPEN Limit Switch Actuator WA Retaining Plate SAFETY (Aux. Close) Limit Switches (1 Required for SS90 Input) Aux. OPEN Limit Switches (1 Required for SS90 Input) 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

7
TO AVOID SERIOUS PERSONAL INJURY OR DEATH
FROM ELECTROCUTION, DISCONNECT ELECTRIC
POWER BEFORE MANUALLY MOVING LIMIT NUTS.
WARNING
LIMIT SWITCH ADJUSTMENT
MAKE SURE THE LIMIT NUTS ARE POSITIONED BETWEEN THE LIMIT SWITCH ACTUATORS BEFORE PRO-
CEEDING WITH ADJUSTMENTS.
ELECTRIC SENSING EDGES
Electric sensing edges with an isolated normally open
(N.O.) output are compatible with your operator.
If your
door does not have a bottom sensing edge and you wish
to purchase one, contact the supplier of your operator.
If not pre-installed by the door manufacturer, mount the
sensing edge on the door according to the instructions
provided with the edge.
The sensing edge may be elec-
trically connected by either coiled cord or take-up reel.
Refer to the steps below
Important Notes:
a)
Proceed with Limit Switch Adjustments before mak-
ing any sensing edge wiring connections to operator
as described below.
b)
Electrician must hardwire the junction box to the
operator electrical box in accordance with local
codes.
ENTRAPMENT PROTECTION ACCESSORIES (OPTIONAL)
TAKE-UP REEL:
Take-up reel should be installed 12"
above the top of the door.
COIL CORD:
Connect operator end of coil cord to junc-
tion box (not supplied) fastened to the wall approximate-
ly halfway up the door opening.
Retaining Plate
CLOSE
Limit Switch
SAFETY
(Aux. Close) Limit Switches
(1 Required for SS90 Input)
OPEN
Limit Switch
1.
To adjust limit nuts depress retaining plate to allow nut
to spin freely.
After adjustment, release plate and
ensure it seats fully in slots of both nuts.
2. To
increase
door travel, spin nut
away
from actuator.
To
decrease
door travel, spin limit nut
toward
actua-
tor.
3. Adjust open limit nut so that door will stop in open
position with the bottom of the door even with top of
door opening.
4. Repeat Steps 1 and 2 for close cycle. Adjust close
limit nut so that actuator is engaged as door fully
seats at the floor.
Actuator
Aux. OPEN
Limit Switches
(1 Required for SS90 Input)
AN ELECTRIC SENSING EDGE IS REQUIRED WHEN
USING THIS OPERATOR IN CONJUNCTION WITH
THE SS90 FIRE DOOR CONTROLLER.
WARNING
IT IS STRONGLY RECOMMENDED THAT A
SENSING EDGE OR OTHER ENTRAPMENT PRO-
TECTION DEVICE BE USED IN CONJUNCTION
WITH THIS OPERATOR.