Rheem 95 Direct Vent Indoor Series Use and Care Manual - Page 14

Vertical Vent Installation, Vertical Vent Termination Location

Page 14 highlights

Installing the water heater: Vertical Vent Termination Location Only Rheem approved termination and parts should be used during installation. The location of the vent terminal depends on the following minimum clearances and considerations (see diagram at left): M inimum twelve (12) inches (30 cm) above roof.2 M inimum twelve (12) inches (30 cm) above anticipated snow level. M aximum twenty-­four (24) inches (60 cm) above roof level without additional support for vent. Vent Pipe Through Roof Min. 12" (30 cm) Above Roof 1 Min. 12" (30 cm) Above Anticipated Snow Level. Max. 24" (60 cm) Above Roof (Without Additional Support) F our (4) feet (1.2 m) from any gable, dormer or other roof structure with building interior access (i.e., vent, window, etc.). T en (10) feet (3 m) from any forced air inlet to the building. Any fresh or make-­up air inlet such as a dryer or furnace area is considered to be a forced air inlet.3 1 Min. 18" (46 cm) Above Roof for installations in Canada. 2 For installations in Canada 18" (45.7 cm). 3 For installations in Canada 6' (1.8 m). Vertical Vent Installation Notice: Only Rheem approved termination and parts should be used during installation. Notice: Follow vent manufacturer's installation instructions and their required clearances to combustibles as required. A fire stop plate should be installed at every penetration of a floor or ceiling if the vent is not running in a fire-­rated shaft. Maintain the required air space clearance to combustible materials and building insulation. Once the vent terminal location has been determined, make a hole through the roof and interior ceiling to accommodate the vent pipe. Complete the vent pipe installation to the water heater's vent connector fitting on the water heater vent collar outlet. Support Storm Collar 3"/ 5" Concentric Pipe Support Clamp Chase Requires 0" (0 cm) Clearance to Combustibles Concentric Vent Pipe has 0" Clearance Requirment Vertical Termination Air Intake Adjustable Roof Flashing Firestop/Support Plate vertical or horizontal runs as previously mentioned. If required, use silicone sealant at the point the vent connector joins the water heater. Install adequate flashing where the vent pipe passes through the roof. Determine the vent terminal height and install the vent pipe accordingly. Refer to the diagram above for proper vent terminal height. The vent roof system must terminate at least 1 foot (30 cm) above the roof line and at least 2 feet (61 cm) higher than any portion of the building within 10 feet (3 m). Install supports every 5 feet (1.5 m) vertically along the vent pipe route. Vertical supports are required after every transition to vertical and are required after every offset elbow. When the vent is free-­standing and penetrates a roof/ceiling, another means of support must be used at a second location. Follow the vent manufacturer's recommended installation instructions provided with the vent purchased from the manufacturer. 1/4" per foot upward slope on horizontal run Firestop 12" (min) (30 cm) Support Hanger Condensate Drain Line Form a Trap in the drain line. Vertical Vent Installation with Horizontal offset Straight Vertical Vent Installation To Drain: Dispose of condensate in accordance to local codes 14 Standard Vertical Vent Termination AP15317 (10_09) DV Gas Manual 10 30 09.indd 14 11/9/2009 3:10:26 PM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36

Installing the water heater:
Vertical Vent Installation
A fire stop plate should be installed at every
penetration of a floor or ceiling if the vent is
not running in a fire°rated shaft. Maintain the
required air space clearance to combustible
materials and building insulation.
Once the vent terminal location has been
determined, make a hole through the roof and
interior ceiling to accommodate the vent pipe.
Complete the vent pipe installation to the
water heater’s vent connector fitting on the
water heater vent collar outlet. Support
vertical or horizontal runs as previously
mentioned. If required, use silicone sealant
at the point the vent connector joins the
water heater.
Install adequate flashing where the vent
pipe passes through the roof. Determine the
vent terminal height and install the vent pipe
accordingly. Refer to the diagram above for
proper vent terminal height.
The vent roof system must terminate at least
1 foot (30 cm) above the roof line and at least
2 feet (61 cm) higher than any portion of the
building within 10 feet (3 m).
Install supports every 5 feet (1.5 m) vertically
along the vent pipe route. Vertical supports
are required after every transition to vertical
and are required after every offset elbow.
When the vent is free°standing and penetrates
a roof/ceiling, another means of support must
be used at a second location.
Follow the vent manufacturer’s recommended
installation instructions provided with the
vent purchased from the manufacturer.
Chase Requires
0" (0 cm) Clearance
to Combustibles
Firestop
Firestop/Support Plate
Adjustable
Roof
Flashing
Concentric
Vent Pipe has
0” Clearance
Requirment
Storm
Collar
Support
Clamp
1/4" per foot upward
slope on horizontal run
Vertical
Termination
Air Intake
3“/ 5” Concentric Pipe
Condensate
Drain Line
Form a Trap
in the drain
line.
To Drain: Dispose
of condensate in
accordance to
local codes
Support
Hanger
Vertical Vent Installation
with Horizontal offset
Straight Vertical
Vent Installation
12” (min)
(30 cm)
Standard Vertical Vent Termination
Vertical Vent Termination Location
The location of the vent terminal depends on the following
minimum clearances and considerations (see diagram at left):
Minimum twelve (12) inches
(30 cm)
above roof.
2
Minimum twelve (12) inches
(30 cm)
above anticipated
snow level.
Maximum twenty°four (24) inches
(60 cm)
above roof level
without additional support for vent.
Four (4) feet
(1.2 m)
from any gable, dormer or other
roof structure with building interior access (i.e., vent,
window, etc.).
Ten (10) feet
(3 m)
from any forced air inlet to the building.
Any fresh or make°up air inlet such as a dryer or furnace
area is considered to be a forced air inlet.
3
2
For installations in Canada 18" (45.7 cm).
3
For installations in Canada 6' (1.8 m)
.
Notice: Only Rheem
approved termination
and parts should be used
during installation.
Notice: Follow vent
manufacturer’s installation
instructions and their
required clearances to
combustibles as required.
14
Min. 12"
(30 cm)
Above Roof
1
Min. 12"
(30 cm)
Above Anticipated Snow Level.
Max. 24"
(60 cm)
Above Roof (Without Additional Support)
1
Min. 18" (46 cm) Above Roof for installations in Canada.
Vent Pipe
Through Roof
Only Rheem approved
termination and parts
should be used during
installation.
AP15317 (10_09)
DV Gas Manual 10 30 09.indd
14
11/9/2009
3:10:26 PM