< Low Ambient Cooling Operation >
![]() |
View all Sanyo CLM2472 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 48 highlights
< Low Ambient Cooling Operation > NOTE The following descriptions of low ambient cooling operation are applied only to CLM1972 and CLM2472 When the outdoor air temperature reaches 57.2 °F (14 °C ) or less during the cooling operation, the operation mode is switched to low ambient cooling operation. When the mode is switched from cooling opration to low ambient cooling operation, the compressor is stopped for 150 seconds temporarily. When the mode has been switched to low ambient cooling operation, the outdoor fan speed is lowered as the outdoor air temperature falls. Outdoor fan speed [ rpm ] 32 °F ( °C ) Outdoor air temperature When the outdoor air temperature reaches 62.6 °F (17 °C ) or more during the low ambient cooling operation, the operation mode is switched to cooling operation. The following protective actions are available to prevent the compressor from operating with abnormal loads. At that time, they initiate thermo-off ( stopping the outdoor unit ) of the air conditioner. Indoor unit : KMS0772 KMS0972 KMS1272 Outdoor air temp. °F ( °C ) 23 (-5) 19.4 (-7) Compressor ON Indoor fan OFF ON ON Indoor unit : KMS1872 KMS2472 Outdoor air temp. °F ( °C ) 32 (0) 28.4 (-2) Compressor ON Indoor fan OFF ON ON 48