Sanyo CM1972 Service Manual - Page 21
Indoor unit, Outdoor unit
![]() |
View all Sanyo CM1972 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 21 highlights
Outdoor Unit CM3172 Indoor unit Wide tube O.D.3/8" O.D.3/8" O.D.1/2" O.D.1/2" Service valve on wide tube DW CW BW AW Header Outdoor unit Sub Main accumulator accumulator High pressure switch H.P. Narrow tube O.D.1/4" O.D.1/4" O.D.1/4" O.D.1/4" Service valve on narrow tube DN Electric expansion valve M CN M BN M AN M Strainer Header Heat exchanger Compressor Cooling cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation Thickness: Min.5/16"(8 mm) should be a min.5/16"(8 mm). CAUTION After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack. Wide tube Insulation Thickness: Min.5/16"(8 mm) Narrow tube 21