Sanyo CM1972 Service Manual - Page 48
Trouble Diagnosis by Error Monitor Lamps
![]() |
View all Sanyo CM1972 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 48 highlights
8-2. Trouble Diagnosis by Error Monitor Lamps To prevent electric shock, do not inspect or repair until WARNING the Power Lamp on the P.C.Board is turned off. 8-2-1. Location of the Error Monitor Lamps Remove the top plate of outdoor unit and the cover of Electrical Component Box. The Power Lamp and Error Monitor Lamps are located on the P.C.Board of Electrical Component Box. (Fig.1) Heat Exchanger Rear side P.C.Board of Electrical Component Box. Error Monitor Lamps Power Lamp ERR0 ERR1 ERR2 ERR3 Front side Fig.1 View from top 8-2-2. Display of the Error Monitor Lamps If a protective device has activated or there is a sensor failure in the outdoor unit, the 4 error monitor lamps on the outdoor control circuit board will indicate the nature of the trouble. : ON : OFF Error Monitor Lamp ERR0 ERR1 ERR2 ERR3 Error Contents Sensor for compressor discharge temp Sensor for heat excharge temp Sensor for branch pipe A (Narrow tube) Sensor for branch pipe B (Narrow tube) Sensor for branch pipe C (Narrow tube) Sensor for branch pipe D (Narrow tube) Outdoor temp sensor Sensor for branch pipe A (Wide tube) Sensor for branch pipe B (Wide tube) Sensor for branch pipe C (Wide tube) Sensor for branch pipe D (Wide tube) HIC circuit trouble (current, temp) Actuation of comp over load relay Actuation of freeze protection function Outdoor unit error. Detail of error message indicate on indoor LED 48