Sanyo CM1972 Service Manual - Page 35
CM3172, KMS2472
![]() |
View all Sanyo CM1972 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 35 highlights
Outdoor Unit CM3172 Indoor Unit KMS2472 × 1 Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 60Hz) (1) Low pressure performance chart 174 (1.2) Lo fan Hi fan 146 (1.0) Low pressure at wide tube service valve psig (MPaG) 118 (0.8) 90 (0.6)77 (25) Indoor air temp. 86°F (30°C) 80°F (27°C) 75°F (24°C) 86 95 104 (30) (35) (40) Outdoor air temperature °F (°C) Operating current (A) (2) Operating current performance chart 12 Lo fan 11 10 Ind8o0o7°r5F°aF(i2r (7t2e°4Cm°)pC.)86°F (30°C) 9 Hi fan 8 77 86 95 104 (25) (30) (35) (40) Outdoor air temperature °F (°C) (3) Indoor discharge air performance chart Indoor discharge air temperature °F (°C) 68.0(20) Lo fan Hi fan 64.4(18) 60.8(16) 57.2(14) 53.6(12) 50.0(10) Indoor air temp. 86°F (30°C) 80°F (27°C) 75°F (24°C) 46.4( 8) 77 86 95 104 (25) (30) (35) (40) Outdoor air temperature °F (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary. 35