Sanyo CMH3172 Service Manual - Page 31
Temperature Charts CM3172
View all Sanyo CMH3172 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 31 highlights
5-1-3. Temperature Charts (CM3172) Outdoor Unit CM3172 Indoor Unit KMS0772 × 1 Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (230V, 60Hz) (1) Low pressure performance chart 174 (1.2) Lo fan Hi fan Hi fan HH fan Low pressure at wide tube service valve psig (MPaG) 146 (1.0) 118 (0.8) Indoor air temp. 86°F (30°C) 80°F (27°C) 75°F (24°C) 90 (0.6)77 86 95 104 (25) (30) (35) (40) Outdoor air temperature °F (°C) (2) Operating current performance chart 5 Lo fan Hi fan Hi fan HH fan 4 Indoor air temp. 86°F (30°C) 8705°°FF((2274°°CC)) Operating current (A) 3 77 86 95 104 (25) (30) (35) (40) Outdoor air temperature °F (°C) (3) Indoor discharge air performance chart Indoor discharge air temperature °F (°C) 68.0(20) Lo fan Hi fan Hi fan HH fan 64.4(18) 60.8(16) 57.2(14) 53.6(12) 50.0(10) Indoor air temp. 86°F (30°C) 80°F (27°C) 75°F (24°C) 46.4( 8) 77 86 95 104 (25) (30) (35) (40) Outdoor air temperature °F (°C) NOTE • This performance chart shows operation of a single wall-mounted indoor unit. The performance chart will vary depending on the indoor unit type. • Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. (In this case, be sure to stop all the indoor units where performance is not being checked.) • The performance is for a tubing length of 24.6ft (7.5m). If the tubing length is different, the performance chart will vary. 31