Sanyo CMH3172 Service Manual - Page 87

Test Run

Page 87 highlights

Regulations on wire size differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Make sure that the installation fully complies with all local and national regulations. (1) Remove access panel "C". (Fig. 32) (2) Connect the inter-unit and power supply line according to the drawing on the panel side. (3) Be sure to size each wire allowing approx. 4" (10 cm) longer than the required length for wiring. Store excess wiring inside the cabinet. (4) When connections are completed, check that all connections are correct as shown in the wiring system diagram on panel side. (5) Be sure to ground the unit according to your local codes. 6. Test Run Performing a test run G Refer to the test run procedures in the indoor unit installation manual. G Perform the test run separately for each connected indoor unit. If 2 units are operated simultaneously, it is not possible to correctly check for errors in tubing and wiring. Checking tubing and wiring Perform the test run and check that operation is normal. If there is an error in tubing or wiring, the refrigerant may flow to indoor unit B when indoor unit A is operated (for example). CAUTION G Stop operation immediately if there is an error in tubing or wiring. Turn the power (breaker) to OFF, and check whether the inter-unit cables are connected incorrectly, or whether the narrow tubes A and B are connected in reverse. Correct the connections. G If there is an error in tubing, pump-down must be performed. Be sure to perform pump-down. After making corrections, again purge the air from the tubes. Lock nut Cabinet Terminal block Conduit plate Plug Access panel "C" Inter unit (Conduit) Power supply (Conduit) Fig. 32 Access panel C Conduit plate CAUTION Make sure there is no gap between access panel "C" and the conduit plate. Fig. 33 25

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99

25
Regulations on wire size differ from locality to locality. For
field wiring requirements, please refer to your local electri-
cal codes. Make sure that the installation fully complies
with all local and national regulations.
(1)
Remove access panel “C”. (Fig. 32)
(2)
Connect the inter-unit and power supply line accord-
ing to the drawing on the panel side.
(3)
Be sure to size each wire allowing approx. 4"
(10 cm) longer than the required length for wiring.
Store excess wiring inside the cabinet.
(4)
When connections are completed, check that all con-
nections are correct as shown in the wiring system
diagram on panel side.
(5)
Be sure to ground the unit according to your local
codes.
Fig. 32
Lock
nu
t
Co
n
d
u
it
plate
Pl
ug
I
n
ter
un
it
(Co
n
d
u
it)
Power
su
pply
(Co
n
d
u
it)
Cabi
n
et
Termi
n
al
block
Acce
ss
pa
n
el “C”
6.
Test Run
Performing a test run
Refer to the test run procedures in the indoor unit
installation manual.
Perform the test run separately for each connected
indoor unit. If 2 units are operated simultaneously, it is
not possible to correctly check for errors in tubing and
wiring.
Checking tubing and wiring
Perform the test run and check that operation is normal.
If there is an error in tubing or wiring, the refrigerant may
flow to indoor unit B when indoor unit A is operated (for
example).
Stop operation immediately if there is an error in tubing
or wiring. Turn the power (breaker) to OFF, and check
whether the inter-unit cables are connected incorrectly,
or whether the narrow tubes A and B are connected in
reverse. Correct the connections.
If there is an error in tubing, pump-down must be per-
formed. Be sure to perform pump-down. After making
corrections, again purge the air from the tubes.
CAUTION
Fig. 33
Co
n
d
u
it plate
Make
su
re there i
s
n
o
g
ap betwee
n
acce
ss
pa
n
el “C” a
n
d the co
n
d
u
it plate.
Acce
ss
pa
n
el
C
CAUTION