Tripp Lite SU2200RTXLCD2U Owner's Manual for Single-Phase Online Rack UPS with - Page 20

Disable, Scroll, Select

Page 20 highlights

Operation 4 The OVERLOAD ALARM selection screen will appear. OVERLOAD ALARM refers to the point at which the UPS will sound its' overload alarm. The factory setting of 105% will provide adequate overload warnings for most applications, but alternative values from 5% to the 105% default (in 5% intervals) are available for custom configurations. To Advance to To Change This the Next Screen: Setting: Press SCROLL (v) Press "SELECT" (^) 105%* SCROLL SELECT Press "SELECT" (^) to SET this value. Press "SCROLL" (v) to advance to the next option. Available values are: 5% to 105% (in 5% intervals) 5 The SHUTDOWN AFTER selection screen will appear. Scroll through available values and press SELECT (^) to SET. Factory default = 105% SHUTDOWN AFTER refers to the amount of runtime the UPS will provide in a power failure before turning off. The factory configuration of DISABLE is suitable for applications where the longest possible runtime is desired. In cases where a specific amount of runtime is needed (and no more), you can set the shutdown-after value to a specific number between 5 and 90 minutes (in 5 min. intervals), using this control. To Advance to To Change This the Next Screen: Setting: Press SCROLL (v) Press "SELECT" (^) DISABLE* SCROLL SELECT Press "SELECT" (^) to SET this value. Press "SCROLL" (v) to advance to the next option. Available values are: 5 to 90 minutes (in 5 min. intervals) 6 The BATTERY SAVE selection screen will appear. Scroll through available values and press SELECT (^) to SET. Factory default = DISABLE BATTERY SAVE option enables automatic UPS power-off in battery mode when there is no need for continued operation. This option prevents unnecessary battery discharge by shutting off UPS power once the load level falls below a user-selectable percentage for 10 continuous minutes. Settings are available to enable shutdown at load levels between 5% and 95% (in 5% increments). This feature is ideal for non-monitored UPS configurations where connected equipment consumes a significant amount of UPS capacity but is subsequently shutdown, or when devices are connected to a UPS but are not powered on to begin with, and thus require no battery backup. Users may determine the ideal percentage setpoint by monitoring the UPS LCD load level screen for typical power consumption in both operating and shutdown modes. For example, if your equipment normally consumes 40-100% UPS capacity while operational, but drops to 3% once it's shutdown, a BATTERY SAVE percentage setting of 5% would be ideal. Once connected equipment power consumption falls below the selected percentage for 10 continuous minutes, the UPS will turn off automatically, preventing unnecessary battery discharge. The factory default for this option is DISABLE. To Advance to To Change This the Next Screen: Setting: Press SCROLL (v) Press "SELECT" (^) DISABLE* SCROLL SELECT Press "SELECT" (^) to SET this value. Press "SCROLL" (v) to advance to the next option. Available values are: 5% to 95% (in 5% intervals) Scroll through available values and press SELECT (^) to SET. Factory default = DISABLE Continued on page 21. 20 12-488-93-3156.indb 20 9/12/2012 3:57:07 PM

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92

 


105%*
SCROLL
SELECT
 


DISABLE*
SCROLL
SELECT
 


DISABLE*
SCROLL
SELECT
Continued on page 21.
20
Operation
4
The OVERLOAD ALARM selection screen will appear.
OVERLOAD ALARM refers to the point at which the UPS will sound its’ overload alarm.
The
factory setting of 105% will provide adequate overload warnings for most applications, but
alternative values from 5% to the 105% default (in 5% intervals) are available for custom
configurations.
5
The SHUTDOWN AFTER selection screen will appear.
SHUTDOWN AFTER refers to the amount of runtime the UPS will provide in a power failure
before turning off. The factory configuration of DISABLE is suitable for applications where the
longest possible runtime is desired. In cases where a specific amount of runtime is needed
(and no more), you can set the shutdown-after value to a specific number between 5 and
90 minutes (in 5 min. intervals), using this control.
6
The BATTERY SAVE selection screen will appear.
BATTERY SAVE option enables automatic UPS power-off in battery mode when there is no
need for continued operation. This option prevents unnecessary battery discharge by shutting
off UPS power once the load level falls below a user-selectable percentage for 10 continuous
minutes. Settings are available to enable shutdown at load levels between 5% and 95% (in
5% increments). This feature is ideal for non-monitored UPS configurations where connected
equipment consumes a significant amount of UPS capacity but is subsequently shutdown, or
when devices are connected to a UPS but are not powered on to begin with, and thus
require no battery backup. Users may determine the ideal percentage setpoint by monitoring
the UPS LCD load level screen for typical power consumption in both operating and
shutdown modes. For example, if your equipment normally consumes 40-100% UPS
capacity while operational, but drops to 3% once it’s shutdown, a BATTERY SAVE percentage
setting of 5% would be ideal. Once connected equipment power consumption falls below the
selected percentage for 10 continuous minutes, the UPS will turn off automatically,
preventing unnecessary battery discharge. The factory default for this option is DISABLE.
To Change This
Setting:
Press “SELECT” (
^
)
Press “SELECT” (
^
) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are: 5% to 105%
(in 5% intervals)
Scroll through available values and press
SELECT (
^
) to SET.
Factory default = 105%
To Advance to
the Next Screen:
Press SCROLL (
v
)
To Change This
Setting:
Press “SELECT” (
^
)
Press “SELECT” (
^
) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are: 5 to 90 minutes
(in 5 min. intervals)
Scroll through available values and press
SELECT (
^
) to SET.
Factory default = DISABLE
To Advance to
the Next Screen:
Press SCROLL (
v
)
To Change This
Setting:
Press “SELECT” (
^
)
Press “SELECT” (
^
) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are: 5% to 95% (in 5% intervals)
Scroll through available values and press
SELECT (
^
) to SET.
Factory default = DISABLE
To Advance to
the Next Screen:
Press SCROLL (
v
)
12-488-93-3156.indb
20
9/12/2012
3:57:07 PM