Tripp Lite SU3000RTXL3UHV Owner's Manual for SmartOnline UPS 932609 - Page 14
Storage and Service, Specifications
View all Tripp Lite SU3000RTXL3UHV manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 14 highlights
200608121 93-2609 SU Owner's Manual.qxd 10/3/2006 3:32 PM Page 14 Storage and Service Storage First turn your UPS OFF: press the "OFF" switch to turn power off at the UPS outlets, then disconnect the power cord from the wall outlet. Next, disconnect all equipment to avoid battery drain. If you plan on storing your UPS for an extended period of time, fully recharge the UPS batteries once every three months by plugging the UPS into a live AC outlet and letting the UPS charge for 4-6 hours. If you leave your UPS batteries discharged for an extended period of time, they may suffer permanent loss of capacity. Service If returning your UPS to Tripp Lite, please carefully pack the UPS using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt. Specifications All Models: Input Frequency (50/60 Hz Auto-Selecting); Output Waveform in Line and Battery Modes (Pure Sine Wave); Transfer Time: (0 ns.); Maximum Harmonic Distortion with Linear Load (< 3%); Maximum Harmonic Distortion with Nonlinear Load (< 6%); Battery Recharge Time to 80% Capacity (2-4 hours). Model Input Voltage (< 70% Load): Input Voltage (Full Load): Output Voltage: Input Breaker Rating: Input Plug Type: Recommended Utility Amps: Output Capacity (VA/Watts): Battery Runtime (Half Load/Full Load) Min.: System Battery Voltage: Approvals: SU1000RTXL2U 65-138V 80-138V 120V 15A 5-15P 15A 1000/800 18/6 36 VDC UL, cUL, FCC, NOM SU1000RTXL2UHV 130-275V 160-275V 208V 8A 6-15P 15A 1000/800 18/6 36 VDC UL, cUL, FCC, NOM SUINT1000RTXL2U 130-275V 160-275V 230V 8A IEC 320-C14 10A 1000/800 18/6 36 VDC CE Model: Input Voltage (< 70% Load): Input Voltage (Full Load): Output Voltage: Input Breaker Rating: Input Plug Type: Recommended Utility Amps: Output Capacity (VA/Watts): Battery Runtime (Half Load/Full Load) Min.: System Battery Voltage: Approvals: SU1500RTXL2U 65-138V 80-138V 120V 20A 5-15P 20 A 1500/1200 17/5 48 VDC UL, cUL, FCC, NOM SU1500RTXL2UHV 130-275V 160-275V 208V 10A 6-20P 15 A 1500/1200 17/5 48 VDC UL,cUL, FCC, NOM SUINT1500RTXL2U 130-275V 160-275V 230V 10A IEC 320-C14 15 A 1500/1200 17/5 48 VDC CE Model Input Voltage (< 70% Load): Input Voltage (Full Load): Output Voltage: Input Breaker Rating: Input Plug Type: Recommended Utility Amps: Output Capacity (VA/Watts): Battery Runtime (Half Load/Full Load) Min.: System Battery Voltage: Approvals: SU2200RTXL2U 65-138V 80-138V 120V 30A 5-20P 20A 2200/1600 18/6 48 VDC UL, cUL, FCC, NOM SU2200RTXL2UHV 130-275V 160-275V 208V 15A 6-20P 20A 2200/1600 18/6 48 VDC UL, cUL, FCC, NOM SUINT2200RTXL2U 130-275V 160-275V 230V 15A IEC 320-C20 20A 2200/1600 18/6 48 VDC CE 14