Whirlpool CGM2751KQ Installation Instructions - Page 4

m°'wP - parts

Page 4 highlights

An exhaust hood should cap the exhaust vent to prevent exhausted air from returning into the dryer, The outlet of the hood must be at least 12 inches (30,5 cm) from the ground or anything else that may be in the path of the exhaust, Four-inch outlet hood is preferred. However, a 2-1/2-inch (6,4 cm) outlet exhaust hood may be used, A 2-1/2-inch (6,4 cm) outlet creates greater back pressure than other hood Iypes, For permanent installation, a stationary exhaust system is required, A main exhaust vent can be used for exhausting a group of dryers, Main exhaust vent should be sized to remove 200 CFM of air per dryer, Large-capacily lint screens of proper design may be used in the main exhaust vent if checked and cleaned frequently, The room where the dryers are located should have make-up air equal to or greater than the CFM of all the dryers in the room, Back-draft Damper Kits, Part No, 3391910, are available from your Whirlpool dealer and should be installed in each dryer's exhaust vent to prevent exhausted air from returning into the dryers and to keep the exhaust in balance within the main exhaust vent, Unobstructed air openings are required, Each exhaust vent should enter the main vent at an angle pointing in the direction of the airflow, Vents entering from the opposite side should be staggered to reduce the exhausted air from interfering with the other vents, The maximum angle of each vent entering the main vent should be no more than 30 +, Keep air openings free of dry cleaning fluid fumes. Fumes create acids which, when drawn through the dryer heating units, can damage dryers and loads being dried. A clean-out cover should be located on the main exhaust vent for periodically cleaning of the exhaust system, Page 4 An exhaust hood should cap the outside end of the main vent to prevent exhausted air from returning to the dryers, If an exhaust hood cannot be used, the outside end of the main vent should have a sweep elbow directed downward, If the main vent travels vertically through the roof, rather than through the wall, install 180 ° sweep elbow on the end of vent at least 2 feet (61 cm) above the highest part of the building, The opening wall or roof shall have a diameter 1/2 inch (1,3 cm) larger than the exhaust vent diameter, The exhaust vent should be centered in the opening, exhaust hood or _[ wall Gas requirements Explosion Hazard Use a new AGA or CSA approved gas supply line. Install a shut-off valve. m°'wP i ho"Ta'ven' main exhaust vent 2 ft. (61 cm) min. above highest point of building _.--_ wall 180° _op _j/elbow main collector vent Securely tighten all gas connections. If connected to LP, have a qualified person make sure gas pressure does not exceed t3" (33 cm) water column. Examples of a qualified person include licensed heating personnel, authorized gas company personnel, and authorized service personnel. Failure to do so can result in death, explosion, or fire. OBSERVEALLGOVERNING CODES AND ORDINANCES. Do Not install screening or cap over end of vent, Am This installation must conform with local codes, or in absence of local codes with the National Fuel Gas Code ANSI Z223,1/NFPA 54 or the CAN/CGA - B149 installation codes, B mThe design of this dryer has been certified by the CSA International for use at altitudes up to 10,000 feet (3048 m) above sea level at the B,T,U, rating indicated on the model/serial plate, Burner input adjustments are not required when the dryer is operated up to this elevation, When installed above 10,000 feet (3048 m), a four percent (4%) reduction of the burner B,T,U, rating shown on the model/serial plate is required for each 1,000 foot (305 m) increase in elevation, For assistance when converting to other gas Iypes and/or installing above 10,000 feet (3048 m) elevation, contact your local service company,

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26

An exhaust
hood
should
cap
the
exhaust
vent
to prevent
exhausted
air
from
returning
into the
dryer,
The
outlet
of the
hood
must be at least
12 inches
(30,5 cm)
from
the
ground
or anything
else that
may
be
in the
path
of the
exhaust,
Four-inch outlet
hood is preferred.
However,
a 2-1/2-inch
(6,4 cm)
outlet
exhaust
hood
may
be used,
A
2-1/2-inch
(6,4 cm)
outlet
creates
greater
back
pressure
than
other
hood
Iypes,
For permanent
installation,
a stationary
exhaust
system
is required,
A main exhaust vent
can
be
used for
exhausting
a group
of dryers,
Main
exhaust
vent
should
be sized to
remove
200 CFM of air per dryer,
Large-capacily
lint screens
of proper
design
may
be used
in the
main
exhaust
vent
if checked
and
cleaned
frequently,
The room
where
the
dryers
are
located
should
have
make-up
air
equal
to or greater
than
the
CFM of
all the
dryers
in the
room,
Back-draft
Damper
Kits,
Part No,
3391910, are
available
from
your
Whirlpool
dealer
and
should
be
installed
in each
dryer's
exhaust
vent
to prevent
exhausted
air from
returning
into the
dryers
and
to keep
the
exhaust
in balance
within
the
main
exhaust
vent,
Unobstructed
air
openings
are
required,
Each exhaust vent
should
enter
the
main
vent
at an angle
pointing
in
the
direction
of the
airflow,
Vents
entering
from
the
opposite
side should
be
staggered
to reduce
the
exhausted
air from
interfering
with
the
other
vents,
The
maximum
angle
of each
vent
entering
the
main vent
should
be no
more
than
30 +,
Keep air openings
free of dry
cleaning
fluid fumes.
Fumes create
acids which,
when drawn
through
the
dryer heating
units, can damage
dryers and
loads being
dried.
A
clean-out
cover
should
be located
on the
main
exhaust
vent
for
periodically
cleaning
of the
exhaust
system,
An
exhaust
hood should
cap
the
outside
end
of the
main vent
to
prevent
exhausted
air from
returning
to the
dryers,
If an exhaust
hood
cannot
be used,
the
outside
end
of
the
main
vent
should
have
a sweep
elbow
directed
downward,
If the
main vent
travels
vertically
through
the
roof,
rather
than
through
the
wall,
install 180
°
sweep
elbow
on the
end
of vent
at
least 2 feet
(61 cm)
above
the
highest
part
of the
building,
The
opening
wall
or roof shall have
a
diameter
1/2
inch (1,3 cm)
larger
than
the
exhaust
vent
diameter,
The
exhaust
vent
should
be
centered
in
the
opening,
exhaust
hood
or
_[
wall
m°'wP
i
ho"Ta'ven'
main
exhaust
vent
wall
180°
_op
2 ft. (61 cm)
_.--_
_j/elbow
min. above
highest point of
building
main collector
vent
Do Not
install screening
or cap
over
end
of vent,
Gas
requirements
Explosion
Hazard
Use a new AGA or CSA
approved
gas supply
line.
Install a shut-off
valve.
Securely
tighten all gas
connections.
If connected
to LP, have a
qualified
person
make sure gas
pressure does not exceed t3"
(33 cm) water column.
Examples
of a qualified
person include
licensed heating
personnel,
authorized
gas company
personnel,
and authorized
service
personnel.
Failure to do so can result in
death,
explosion,
or fire.
OBSERVEALLGOVERNINGCODES
AND ORDINANCES.
Am
This installation
must conform
with
local
codes,
or in absence
of
local
codes
with
the
National
Fuel
Gas Code
ANSI Z223,1/NFPA
54 or the
CAN/CGA
- B149 installation
codes,
B
mThe design
of this dryer
has
been
certified
by the
CSA
International
for use at altitudes
up to
10,000 feet
(3048 m) above
sea level
at the
B,T,U, rating
indicated
on the
model/serial
plate,
Burner
input
adjustments
are
not
required
when
the
dryer
is operated
up to this
elevation,
When
installed
above
10,000 feet
(3048 m), a four
percent
(4%)
reduction
of the
burner
B,T,U, rating
shown
on the
model/serial
plate
is
required
for each
1,000 foot
(305 m)
increase
in elevation,
For assistance
when
converting
to other
gas Iypes
and/or
installing
above
10,000 feet
(3048 m) elevation,
contact
your
local
service
company,
Page
4