Frigidaire GLEH1642FS Installation Instructions (All Languages) - Page 3

Water Supply Requirements, Drain Requirements - volts

Page 3 highlights

ELECTRICAL REQUIREMENTS ELECTRIC Laundry Center NOTE: Do not under any circumstances remove grounding prong from plug. CIRCUIT - Individual 30 amp. branch circuit fused with 30 amp. time delay fuses or circuit breakers. Use separately fused circuits for washers and dryers, and DO NOT operate a washer and a dryer on the same circuit. POWER SUPPLY - 3 wire or 4-wire, 240 volt, single phase, 60 Hz, Alternating Current. Grounding Prong POWER SUPPLY CORD KIT - 3 wire - the dryer MUST employ a 3-conductor power supply cord NEMA 10-30 type SRDT rated at 240 volt AC minimum, 30 amp., with 3 open end spade lug connectors with upturned ends or closed loop connectors and marked for use with clothes dryers. See ELECTRICAL CONNECTIONS FOR A 3-WIRE SYSTEM. 4 wire - The dryer MUST employ a 4-conductor power supply cord NEMA 14-30 type SRDT or ST (as required) rated at 240 volt AC minimum, 30 amp., with 4 open end spade lug connectors with upturned ends or closed loop connectors and marked for use with clothes dryers. See ELECTRICAL CONNECTIONS FOR A 4-WIRE SYSTEM. (Canada - 4-wire power supply cord is installed on dryer.) WATER SUPPLY REQUIREMENTS Hot and cold water faucets MUST be installed within 42 inches (106.68 cm) of your laundry center's water inlet. The faucets MUST be 3/4 inch (1.9 cm) garden hose type so inlet hoses can be connected. Water pressure MUST be between 10 and 120 pounds per square inch (maximum unbalance pressure, hot vs. cold, 10 psi). Your water department can advise you of your water pressure. DRAIN REQUIREMENTS WARNING - Risk of Shock. Appliance grounded to neutral conductor through a link. Grounding through the neutral link is prohibited for (1) New branch circuit installations (2) mobile homes; (3) recreational vehicles; and (4) areas where local codes do not permit grounding through the neutral, (1) disconnect the link from the neutral, (2) use grounding terminal or lead to ground appliance in accordance with local codes and (3) connect neutral terminal or lead to branch circuit neutral in usual manner (if the appliance is to be connected by means of a cord kit, use 4-conductor cord for this purpose). USE COPPER CONDUCTOR ONLY. 1. Drain capable of eliminating 17 gals. per minute. 2. A standpipe diameter of 1¼ inches (3.18 cm) minimum. 3. The standpipe height above the floor should be: Minimum height: 33 inches (83.82 cm) Maximum height: 96 inches (244 cm) OUTLET RECEPTACLE - NEMA 10-30R receptacle to be located so the power supply cord is accessible when the dryer is in the installed position. (Canada - NEMA 14-30R receptacle.) 33" Min. (83.82cm) 96"Max. (244 cm) NEMA 10-30R NEMA 14-30R GAS Laundry Center CIRCUIT - Individual 15 amp minimum branch circuit fused with a time delay fuse or circuit breaker. POWER SUPPLY -3 wire, 120 volt single phase, 60 Hz, Alternating Current. NOTE: For installations requiring a longer drain hose, have a qualified technician install a longer hose, PIN 134049201, available from an authorized parts distributor. For drain systems in the floor, install a siphon break kit, available from your local hardware store . POWER SUPPLY CORD -The gas laundry center is equipped with a 120 volt 3-wire power cord.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

ELECTRICAL REQUIREMENTS
ELECTRIC Laundry Center
CIRCUIT
- Individual 30 amp. branch circuit fused with 30
amp. time delay fuses or circuit breakers.
Use separately fused circuits for washers and dryers, and
DO
NOT
operate a washer and a dryer on the same circuit.
POWER SUPPLY
- 3 wire or 4-wire, 240 volt, single phase, 60
Hz, Alternating Current.
POWER SUPPLY CORD KIT
-
3 wire
- the dryer
MUST
employ
a 3-conductor power supply cord NEMA 10-30 type SRDT rated
at 240 volt AC minimum, 30 amp., with 3 open end spade lug
connectors with upturned ends or closed loop connectors and
marked for use with clothes dryers.
See ELECTRICAL
CONNECTIONS FOR A 3-WIRE SYSTEM.
4 wire
- The dryer
MUST
employ a 4-conductor power supply
cord NEMA 14-30 type SRDT or ST (as required) rated at 240
volt AC minimum, 30 amp., with 4 open end spade lug
connectors with upturned ends or closed loop connectors and
marked for use with clothes dryers. See ELECTRICAL
CONNECTIONS FOR A 4-WIRE SYSTEM.
(Canada - 4-wire power supply cord is installed on dryer.)
WARNING – Risk of Shock.
Appliance grounded to neutral
conductor through a link.
Grounding through the neutral link is
prohibited for (1) New branch circuit installations (2) mobile
homes; (3) recreational vehicles; and (4) areas where local codes
do not permit grounding through the neutral, (1) disconnect the
link from the neutral, (2) use grounding terminal or lead to
ground appliance in accordance with local codes and (3) connect
neutral terminal or lead to branch circuit neutral in usual manner
(if the appliance is to be connected by means of a cord kit, use
4-conductor cord for this purpose).
USE COPPER CONDUCTOR
ONLY.
OUTLET RECEPTACLE
- NEMA 10-30R receptacle to be located
so the power supply cord is accessible when the dryer is in the
installed position. (Canada - NEMA 14-30R receptacle.)
WATER SUPPLY REQUIREMENTS
Hot and cold water faucets
MUST
be installed within 42 inches
(106.68 cm) of your laundry center’s water inlet. The faucets
MUST
be 3/4 inch (1.9 cm) garden hose type so inlet hoses can
be connected. Water pressure
MUST
be between 10 and 120
pounds per square inch (maximum unbalance pressure, hot vs.
cold, 10 psi). Your water department can advise you of your
water pressure.
CIRCUIT
- Individual 15 amp minimum branch circuit fused with
a time delay fuse or circuit breaker.
POWER SUPPLY
-3 wire, 120 volt single phase, 60 Hz,
Alternating Current.
POWER SUPPLY CORD
-The gas laundry center is equipped
with a 120 volt 3-wire power cord.
GAS
Laundry Center
NEMA 10-30R
NEMA 14-30R
NOTE: Do not under
any circumstances
remove grounding
prong from plug.
Grounding Prong
DRAIN REQUIREMENTS
1. Drain capable of eliminating 17 gals. per minute.
2. A standpipe diameter of 1¼ inches (3.18 cm) minimum.
3. The standpipe height above the floor should be:
Minimum height: 33 inches (83.82 cm)
Maximum height: 96 inches (244 cm)
33" Min.
33" Min.
33" Min.
33" Min.
33" Min.
(83.82cm)
(83.82cm)
(83.82cm)
(83.82cm)
(83.82cm)
NOTE:
For installations requiring a longer drain hose, have a
qualified technician install a longer hose,
PIN
134049201,
available from an authorized parts distributor. For drain systems
in the floor, install a siphon break kit, available from your local
hardware store .
96"Max.
96"Max.
96"Max.
96"Max.
96"Max.
(244 cm)
(244 cm)
(244 cm)
(244 cm)