Haier AB092FCBHA User Manual - Page 19

Installation of indoor unit

Page 19 highlights

Installation of indoor unit I. Location 1. Between the ceiling and the upstairs floor. 2. Favorable for water drainage pipes 3. Less than 2.7 meters above the floor for air outlet opening 4. Open for air circulation 5. Away from the area where heavy oily dusts, moisture or steam is likely to accumulate, such as kitchens and workshops 6. Free from sulfurous or irritant gas, including thinner and gasoline 7. Firm enough to hold the weight of the unit 8. Free from TV set, piano or other sensitive articles below 9. At least 1 meter away from TV set and radio H *0.31m II. Preparation for installation 1.5m Airflow Air intake Airflow outlet inlet outlet 1.5m Over2.5m (1) Location of ceiling opening and hanger rod (Front view) 460mm Hanger rod Thickness of the area where the ceiling overlaps decorative board should be over 15mm. Hanger rod pedestal Decorative board 630mm Ceiling 600mm Indoor unit set 575mm Space between each two hanger rods 620mm 335mm 210mm 35mm Space between each two hanger rods 620mm Ceiling Decorative board Indoor unit set 575mm Ceiling 600mm Decorative board 630mm (2)Cut an opening on the ceiling (if any) where the indoor unit is to be installed.Refer to the figure above for specific dimensions. Tubes for refrigerant and water drainage and electrical wires for remote controller, the fun unit and outdoor unit should be well fixed and arranged before installation of the indoor unit. Ceilings should be reinforced to prevent vibration after an opening is made. Consult an architect for necessary measures. 18

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

460mm
Decorative board 630mm
Ceiling 600mm
Indoor unit set 575mm
Ceiling 600mm
Decorative board 630mm
Hanger rod
Indoor unit set 575mm
Space between each two hanger rods 620mm
Space between each two hanger rods 620mm
1.5m
1.5m
*0.31m
H
Over
2.5m
Airflow
outlet
Airflow
outlet
Air intake
inlet
Hanger rod
pedestal
335mm
210mm
35mm
Decorative board
Ceiling
Thickness of the area where the
ceiling overlaps decorative board
should be over 15mm.
1. Between the ceiling and the upstairs floor.
2. Favorable for water drainage pipes
3. Less than 2.7 meters above the floor for air outlet opening
4. Open for air circulation
5. Away from the area where heavy oily dusts, moisture or steam is likely to accumulate,
such as kitchens and workshops
6. Free from sulfurous or irritant gas, including thinner and gasoline
7. Firm enough to hold the weight of the unit
8. Free from TV set, piano or other sensitive articles below
9. At least 1 meter away from TV set and radio
(1)
Location of ceiling opening and hanger rod (Front view)
18
Installation of indoor unit
I. Location
II. Preparation for installation
(2)
Cut an opening on the ceiling (if any) where the indoor unit is to be installed.Refer to the fi-
gure above for specific dimensions.
Tubes for refrigerant and water drainage and electrical wires for remote controller, the fun
unit and outdoor unit should be well fixed and arranged before installation of the indoor unit.
Ceilings should be reinforced to prevent vibration after an opening is made.
Consult an architect for necessary measures.