HP Cisco MDS 9120 Cisco MDS 9500 Series Hardware Installation Guide (OL-17467- - Page 219
Component Power Requirements and Heat Dissipation for the Cisco MDS 9513 Director
View all HP Cisco MDS 9120 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 219 highlights
Appendix D Technical Specifications Power Specifications for the Cisco MDS 9513 Director Send documentation comments to [email protected]. • Two AC power connection @ 220 VAC = 6000 W output If a 110 VAC input is chosen, a 110-VAC power cord (CAB-7513AC=) must be ordered separately. Note Power output does not include the power used by the individual modules used in the chassis. Table D-8 lists the specifications for the Cisco MDS 9513 power supplies. Table D-8 Specifications for Cisco MDS 9513 Power Supplies Description Specification 6000-W AC Power Supply Type Autoranging input with power factor corrector. Voltage 100 to 240 VAC (±10%). Current rating 16 A maximum at 100 to 120 VAC and 2900-W output. 16 A maximum at 200 to 240 VAC and 6000-W output. Frequency 50 to 60 Hz (nominal) (±3 Hz for full range). Output capacity One AC power connection @110 VAC = No output Two AC power connection @110 VAC = 2900 W output One AC power connection @ 220 VAC = 2900 W output One AC power connection @110 VAC and one AC power connection @ 220 VAC = 2900 W output Two AC power connection @ 220 VAC = 6000 W output Output voltage at 110/120 3.3 V at 10 A, 50 V at 57 A Output voltage at 200/240 3.3 V at 10A, 50 V at 119 A Component Power Requirements and Heat Dissipation for the Cisco MDS 9513 Director Consider heat dissipation when sizing the air-conditioning requirements for an installation. The power and heat associated with a Cisco MDS 9513 Director varies based upon the following considerations: • Power supply type • Switching module type and number of switching modules installed • Average switching traffic levels Table D-9 lists the power requirements and heat dissipation for the components of the Cisco MDS 9513 Director. Note Unless noted otherwise, the data listed in Table D-9 is based on worst-case conditions. Typical numbers are approximately 30 percent below the numbers listed here. OL-17467-02 Cisco MDS 9500 Series Hardware Installation Guide D-7