- HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 1
installation instructions hp StorageWorks SAN switch rack mount kit Second Edition (June 2003) Part Number: AV-RU6YB-TE This document provides step-by-step instructions for installing the SAN Switch 2/8, SAN Switch 2/16 or SAN Switch 2/32 using the hp StorageWorks SAN switch rack mount kit. For the - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 2
this document is subject to change without notice. BROCADE, the Brocade B weave logo, Brocade: the Intelligent Platform for Networking Storage, SilkWorm, an additional warranty. Printed in the U.S.A. SAN Switch Rack Mount Kit Installation Instructions Second Edition (June 2003) Part Number: AV-RU6YB - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 3
, please visit the following StorageWorks website: http://www.hp.com/country/us/eng/ prodserv/storage.html. For information about Fibre Channel standards, visit the Fibre Channel Association website, located at: http://www.fibrechannel.org. SAN Switch Rack Mount Kit Installation Instructions 3 - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 4
, the stabilizing feet are attached to the rack. ■ In multiple rack installations, the racks are coupled. ■ Only one rack component is extended at any time. A rack may become unstable if more than one rack component is extended for any reason. 4 SAN Switch Rack Mount Kit Installation Instructions - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 5
in the rack is flowing in the same front-to-back direction. Note: HP highly recommends mounting the switch in a cabinet or rack so that the fans reside in the front of the cabinet, and the ports (cables) reside in the rear of the cabinet. SAN Switch Rack Mount Kit Installation Instructions 5 - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 6
overheating: ■ To ensure adequate cooling, install the switch with the non-port side, which contains the air intake vents electrical codes ■ Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on the switch SAN Switch Rack Mount Kit Installation Instructions - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 7
, the SFP media side of the switch must face the rear of the rack. This mounting allows air to enter from the front of the rack and to exhaust at the rear of the rack, similar to other rack-mounted equipment. This prevents switch overheating. SAN Switch Rack Mount Kit Installation Instructions 7 - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 8
the SAN Switch Rack Mount Kit This section provides instructions for installing the SAN Switch 2/32, SAN Switch 2/16, or SAN Switch 2/8 in an HP System/e rack, or in an HP 9000 Series or comparable EIA rack using the SAN Switch Rack Mount Kit, part number 331148-B21. Figure 1: SAN Switch 2/16 rack - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 9
16-inch Phillips pan-head screw with thread lock (10) #10-32 x 1/2-inch Phillips pan-head screw with captive star lock washer (8) #10 alignment washer (8) #10 adapter washer (2) 1/4-20 hex nut with captive star lock washer (2) 1/4-inch flat washer SAN Switch Rack Mount Kit Installation Instructions - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 10
the two brackets with (2) #10-32 x 1/2-inch Phillips pan-head screws with captive star lock washers and (2) #10 adapter washers as shown in Figure 2. Figure 2: Installing the rear mounting brackets (HP 9000 Series or comparable EIA rack) 10 SAN Switch Rack Mount Kit Installation Instructions - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 11
in Figure 3. Figure 3: Installing the rear mounting brackets (HP System/e rack-left rear upright) Note: This kit contains both left rails and right rails. The rails are marked with Right and Left to distinguish the rails from each other. SAN Switch Rack Mount Kit Installation Instructions 11 - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 12
hex nuts with captive star lock washers attached loosely as shown in Figure 4. Don't tighten them. The nuts will be tightened later in step 8. Figure 4: Installing the outer rails (HP 9000 Series or comparable EIA rack) 12 SAN Switch Rack Mount Kit Installation Instructions - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 13
lock washers and two #10 adapter washers in the upper and lower hole locations of the left rail. See Figure 5. Figure 5: Assembling the outer rails (HP 9000 Series or comparable EIA rack) SAN Switch Rack Mount Kit Installation Instructions 13 - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 14
with thread lock required to assemble the inner rails by referring to Table 1. Table 1: Number of screws required to assemble the inner rails Switch SAN Switch 2/32 SAN Switch 2/16 SAN Switch 2/8 Number of #8-32 x 3/16-inch Screws 12 10 14 14 SAN Switch Rack Mount Kit Installation Instructions - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 15
match up-right inner with right outer and left inner with left outer. Note that the SAN switch mounts in the rack with its front, the port side, facing the back of the rack. The rear of the switch, the AC side, faces the front of the rack. SAN Switch Rack Mount Kit Installation Instructions 15 - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 16
screws. Attaching both inner rails requires ten screws. Figure 7: Assembling the inner rails Note: For factory integration only, tighten the #8-32 x 3/16-inch Phillips pan-head screw with thread lock and torque between 6 to 8 inch-pounds. 16 SAN Switch Rack Mount Kit Installation Instructions - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 17
plenum is not preinstalled on the SAN Switch 2/8, refer to the HP StorageWorks SAN Switch 2/8 Version 3.1.x Installation Guide for complete plenum installation instructions. Figure 8: Assembling the inner rails on a SAN Switch 2/8 with plenum SAN Switch Rack Mount Kit Installation Instructions 17 - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 18
the switch into a rack (HP 9000 Series or comparable EIA rack) Insert the switch into the rack and install (2) #10-32 x 1/2-inch Phillips pan-head screws with captive star lock washers with one on each side. See Figure 9 and Figure 10. 18 SAN Switch Rack Mount Kit Installation Instructions - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 19
/e rack) 8. Tighten the nuts installed in step a of step 4 on page 12. See Figure 4. Note: To uninstall a switch, remove the middle #10-32 x 1/2-inch Phillips pan head screw with captive star lock washer from either side of the rack uprights. SAN Switch Rack Mount Kit Installation Instructions 19 - HP StorageWorks 16-EL | HP StorageWorks SAN Switch Rack Mount Kit Installation I - Page 20
20 SAN Switch Rack Mount Kit Installation Instructions
installation
instructions
hp
StorageWorks
SAN switch
rack mount kit
Second Edition (June 2003)
Part Number:
AV–RU6YB–TE
This document provides step-by-step
instructions for installing the SAN Switch 2/8, SAN Switch
2/16 or SAN Switch 2/32 using the hp StorageWorks SAN switch rack mount kit.
For the latest version of these Installation Instructions and other documentation, access the HP
storage website at:
.