HP Surestore 64 Installation Guide - Page 2

Step 1: Mount the anti-tip feet (HPRosebowlII rack only)

Page 2 highlights

Step 1: Mount the anti-tip feet (HP Rosebowl II rack only) Place the anti-tip feet (A) on the front and back of the rack base. Use the supplied hardware to bolt the feet to the base of the rack. Be sure to lower the rack feet (B) until they touch the floor. Step 2: Select the mounting location for the rail tray The rail tray will be mounted 1U below the switch. Because the switch should be mounted no higher than U11, the tray should be mounted no higher than U10. Make sure there are at least 2Us above the top of the switch empty for the sliding shelf. H 2 of 8

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10

H
2 of 8
Step 1:
Mount the anti-tip feet
(HP Rosebowl II rack only)
Place the anti-tip feet (A) on the front and back of the
rack base. Use the supplied hardware to bolt the feet
to the base of the rack. Be sure to lower the rack feet
(B) until they touch the floor.
Step 2:
Select the mounting location for
the rail tray
The rail tray will be mounted 1U below the switch.
Because the switch should be mounted no higher
than U11, the tray should be mounted no higher than
U10. Make sure there are at least 2Us above the top
of the switch empty for the sliding shelf.