LG LMHM2017ST Installation Instructions - Page 9
Standard, Fittings, calculate, the equivalent, length of each duct piece used, see
View all LG LMHM2017ST manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 9 highlights
Standard Fittings NOTE: If the existing duct is round, you must use a rectangular-to-round adapter, with a rectangular 3" extension duct installed between the damper assembly and the adapter to prevent the exhaust damper's sticking. Duct Length The total length of the duct system, including straight duct, elbows, transitions, and wall or roof caps must not exceed the equivalent of 140 feet. For best performance, do not use more than three 90 degree elbows, and keep length as short as possible. Below are the standard fittings and their equivalent length in feet. 1 3 3 1/4" x 10" to 6"=5ft. 3 1/4" x 10" roof cap=24ft. 3 1/4,,x 10,, 90_ elbow=25ft. 7 90°elbow =1 Oft. 3 1/4" x 10" wall cap =40ft. 45°elbow =5ft. Figure 10 31/4"x10" flat elbow = 1Oft. To calculate the equivalent length of each duct piece used, see the examples below. For 3 1/4"x10" SYSTEMS 3 1/4"xl 0" Exam }les For 6"ROUND SYSTEMS 90 ° elbows _ 6ft. wall cap 90 ° elbow _,_'- 6ft._ t. _ wall cap 1-3 1/4" x 10" 90° elbow = 25ft. 1-Wall Cap 8 feet straight duct TOTAL LENGTH = 40 ft. = 8 ft. = 73 ft. transi_ _/ 1-transition 2-90 ° elbows 1-Wall Cap 8 feet straight TOTAL LENGTH = 5 ft. = 20 ft. = 40 ft. = 8 ft. = 73 ft. -9-