Panasonic 26PSU1U6 Tech Data - Service Manual - Page 128
Leak Test, Evacuation And Additional Refrigerant Charge
View all Panasonic 26PSU1U6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 128 highlights
1-14. LEAK TEST, EVACUATION AND ADDITIONAL REFRIGERANT CHARGE Perform an air-tightness test for this package A/C. Check that there is no leakage from any of the connections. Air and moisture in the refrigerant system may have undesirable effects as indicated below. pressure in the system rises operating current rises cooling (or heating) efficiency drops moisture in the refrigerant circuit may freeze and block capillary tubing water may lead to corrosion of parts in the refrigerant system Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system. 1 Air Purging with a Vacuum Pump (for Test Run) Preparation Check that each tube (both liquid and gas tubes) between the indoor and outdoor units has been properly connected and all wiring for the test run has been completed. Remove the valve caps from both the gas and liquid service valves on the outdoor unit. Note that both liquid and gas tube service valves on the outdoor unit are kept closed at this stage. The refrigerant charge at the time of shipment is only guaranteed sufficient for a tubing length of up to 100 ft. The tubing may exceed this length, up to the maximum permitted length; however, an additional charge is necessary for the amount that the tubing exceeds 100 ft. (No additional refrigerating machine oil is needed.) 1. Leak Test (1) With the service valves on the outdoor unit closed, remove the 1/4 in. flare nut and its bonnet on the gas tube service valve. (Save for reuse.) (2) Attach a manifold valve (with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses. CAUTION Use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept closed. 1. Specifications Manifold gauge Fig. 1-122 Vacuum pump Outlet Inlet Pressure gauge Fig. 1-123 Manifold valve Lo Hi Charge hose Cylinder valve Nitrogen gas cylinder (In vertical standing position) Gas tube Liquid tube Open Close Outdoor unit Close 1-122 Fig. 1-124