Panasonic 26PSU1U6 Tech Data - Service Manual - Page 178
Table of Thermistor Characteristics, Check Pin, Outdoor Air Temp. TO, Intake Temp. TS, Heat
View all Panasonic 26PSU1U6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 178 highlights
4. Service procedures Check Pin Short-circuit the cooling check pin (or heating check pin) on the outdoor unit control PCB to perform the control described below. 1. Thermistor checks The checks listed below are performed for 1 second each, in order from the top down. The results are displayed by LED 1 and 2. Thermistor Discharge temp. (TD) Outdoor air temp. (TO) Heat exchanger temp. (C1) Heat exchanger temp. (C2) Intake temp. (TS) Check results Normal Abnormal LED 1 lit LED 2 lit LED 1 lit LED 1 and 2 OFF LED 1 lit 2. 4-way valve turns ON for 1 second. 3. Forced cooling (or heating) operation 4-4. Table of Thermistor Characteristics (1) Outdoor Air Temp. (TO), Intake Temp. (TS), Heat Exchanger Temp. (C1) Sensor, Heat Exchanger Temp. (C2) Sensor (2) Discharge Temp. (TD) Sensors Resistance (kΩ) Resistance (kΩ) 4 Temperature (˚F) Temperature (°F) 4-14