Tripp Lite 5PXEBM72RTG2 Owners Manual for 5PX1000RTG2 5PX1000RTNG2 5PX1500RTG2 - Page 36

Extended Battery Modules EBMs, LED is On.

Page 36 highlights

The following table describes typical conditions: Conditions Possible cause Battery mode LED is On. 1 beep every 10 seconds A utility failure has occurred and the UPS is in battery mode. Action The UPS is powering the equipment with battery power. Prepare your equipment for shutdown. Battery mode LED is On. 1 beep every 3 seconds The UPS is in Battery mode and the battery is running low. This warning is approximate, and the actual time to shutdown may vary significantly. Depending on the UPS load and number of Extended Battery Modules (EBMs), the "Battery Low" warning may occur before the batteries reach 20% capacity. No battery LED is On Beep continuous The batteries are disconnected. Verify that all batteries are properly connected. If the condition persists, contact your service representative. Battery mode LED is On. Beep continuous The battery test is failed due to bad or disconnected batteries. Verify that all batteries are properly connected. If the condition persists, contact your service representative. The UPS does not provide the expected backup time. The batteries need charging or service. Apply utility power for 48 hours to charge the batteries. If the condition persists, contact your service representative. Power Overload LED is On Power requirements exceed the UPS capacity (greater than 100% of nominal; see "User Settings" for specific output overload ranges). Remove some of the equipment from the UPS. The UPS continues to operate, but may shut down if the load increases. The alarm resets when the condition becomes inactive. UPS Over temperature LED is On 1 beep every 3 seconds The UPS internal temperature is too high or a fan has failed. At the warning level, the UPS generates the alarm but remains in the current operating state. If the temperature rises another 10°C, the UPS shuts down. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. Restart the UPS. If the condition continues to persist, contact your service representative. The UPS does not start The input source is not connected correctly. Check the input and battery connections. 614-40095-00 36

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42

614-40095-00
36
The following table describes typical conditions:
Conditions
Possible cause
Action
Battery mode
LED is On.
1 beep every 10 seconds
A utility failure has occurred and the UPS is in
battery mode.
The UPS is powering the
equipment with battery power.
Prepare your equipment for
shutdown.
Battery mode
LED is On.
1 beep every 3 seconds
The UPS is in Battery mode and the battery is
running low.
This warning is approximate, and
the actual time to shutdown may
vary significantly. Depending on
the UPS load and number of
Extended Battery Modules (EBMs),
the "Battery Low" warning may
occur before the batteries reach
20% capacity.
No battery
LED is On
Beep continuous
The batteries are disconnected.
Verify that all batteries are
properly connected. If the
condition persists, contact your
service representative.
Battery mode
LED is On.
Beep continuous
The battery test is failed due to bad or
disconnected batteries.
Verify that all batteries are
properly connected. If the
condition persists, contact your
service representative.
The UPS does not provide the
expected backup time.
The batteries need charging or service.
Apply utility power for 48 hours to
charge the batteries. If the
condition persists, contact your
service representative.
Power Overload
LED is On
Power requirements exceed the UPS capacity
(greater than 100% of nominal;
see “User Settings” for specific output overload
ranges).
Remove some of the equipment
from the UPS. The UPS continues
to operate, but may shut down if
the load increases. The alarm
resets when the condition
becomes inactive.
UPS Over temperature
LED is On
1 beep every 3 seconds
The UPS internal temperature is too high or a fan
has failed. At the warning level, the UPS
generates the alarm but remains in the current
operating state. If the temperature rises another
10°C, the UPS shuts down.
Clear vents and remove any heat
sources. Allow the UPS to cool.
Ensure the airflow around the UPS
is not restricted. Restart the UPS. If
the condition continues to persist,
contact your service
representative.
The UPS does not start
The input source is not connected correctly.
Check the input and battery
connections.