Campbell Scientific CS616 CS616 and CS625 Water Content Reflectometers - Page 23
CS616 Sample Edlog Program 2
View all Campbell Scientific CS616 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 23 highlights
CS616 and CS625 Water Content Reflectometers 3: Polynomial (P55) 1: 1 Reps 2: 1 X Loc [ period 3: 2 F(X) Loc [ VWC 4: -0.0663 C0 5: -0.0063 C1 6: 0.0007 C2 7: 0.0 C3 8: 0.0 C4 9: 0.0 C5 ] ] 4: Do (P86) 1: 21 Set Flag 1 Low 5: End (P95) *Table 2 Program 02: 0.0000 Execution Interval (seconds) *Table 3 Subroutines End Program -Input Locations- 1 period 1 0 1 2 VWC 1 0 1 6.4.5.2 CS616 Sample Edlog Program 2 Every 5 minutes, measure CS616 output period using instruction 27 and convert to volumetric water content. Write hourly average to datalogger final storage. CS616 green orange CR10X Single-Ended Channel 1 (SE1) Control Port 1 (C1) The red lead is connected to 12 Vdc and the black and shield are connected to ground. ;{CR10X} ; *Table 1 Program 01: 300 Execution Interval (seconds) 1: Do (P86) 1: 41 Set Port 1 High ;Enable/Turn On the CS616 probe. 2: Period Average (SE) (P27) 1: 1 Reps 2: 4 200 kHz Max Freq @ 2 V Peak to Peak, Period Output 3: 1 SE Channel 4: 100 No. of Cycles 5: 1 Timeout (0.01 sec units) 6: 1 Loc [ period ] 7: 1.0 Mult 8: 0.0 Offset 17