Approved Scenarios and Scenarios Not Approved for Dual DC Power Supply Configuration You can connect a single DC power source to either the A input or the B input. If there are dual power sources, connect one source to the A input and one source to the B input. Both sources must be the same polarity (with respect to ground) and voltage (within 0.25 volts). Do not connect -DC grounded and +DC grounded dual sources to Cisco 2811, Cisco 2821, and Cisco 2851 series integrated services routers. Caution Dual sources with opposite-polarity grounding damage equipment. In Figure 21, either the positive source terminal or the negative source terminal is tied to ground. Figure 21 Connecting to One Source Only-Source A or Source B A- A- + + A+ A+ B+ B+ 127037 B- B- In Figure 22, source A and source B share common negative terminal connections. Figure 22 Connecting Source A and Source B with Common Negative Terminals AVa + A+ + B+ Vb B- 127039 In Figure 23, source A and source B share common positive terminal connections. This is allowed only if Va equals Vb (within 0.25 V). Caution When connecting source A and source B with common positive terminals, if source A and source B voltages are unequal by more than 0.25 V, the higher-voltage source can discharge into the lower-voltage source through the Aand B- input terminals. Excessive discharging currents through these terminals can cause one or both of the dual input DC power supply's internal A- or B- fuses to open, resulting in lack of redundancy or system failure. When source A and source B are within 0.25 V, discharge current is minimal. 24

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46

24
Approved Scenarios and Scenarios Not Approved for Dual DC Power Supply Configuration
You can connect a single DC power source to either the A input or the B input. If there are dual power sources, connect one
source to the A input and one source to the B input. Both sources must be the same polarity (with respect to ground) and voltage
(within 0.25 volts). Do not connect –DC grounded and +DC grounded dual sources to Cisco 2811, Cisco 2821, and
Cisco 2851 series integrated services routers.
Caution
Dual sources with opposite-polarity grounding damage equipment.
In Figure 21, either the positive source terminal or the negative source terminal is tied to ground.
Figure 21
Connecting to One Source Only—Source A or Source B
In Figure 22, source A and source B share common negative terminal connections.
Figure 22
Connecting Source A and Source B with Common Negative Terminals
In Figure 23, source A and source B share common positive terminal connections. This is allowed only if Va equals Vb (within
0.25 V).
Caution
When connecting source A and source B with common positive terminals, if source A and source B voltages are
unequal by more than 0.25 V, the higher-voltage source can discharge into the lower-voltage source through the A-
and B- input terminals. Excessive discharging currents through these terminals can cause one or both of the dual
input DC power supply's internal A- or B- fuses to open, resulting in lack of redundancy or system failure. When
source A and source B are within 0.25 V, discharge current is minimal.
A-
127037
A+
B+
B-
+
A-
A+
B+
B-
+
A-
127039
A+
B+
B-
Va
Vb
+
+