Craftsman 30084N Operation Manual - Page 13
Electrical Service Guide, 12. Selecting A Location And Connecting Input Power
UPC - 055249070420
View all Craftsman 30084N manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 13 highlights
2-11. Electrical Service Guide Input Voltage 200 230 Input Amperes At Rated Output 30 26 Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes Circuit Breaker 1, Time-Delay 2 35 30 Normal Operating 3 45 40 Min Input Conductor Size In AWG/Kcmil 10 10 Max Recommended Input Conductor Length In Feet (Meters) 97 128 (29) (39) Min Grounding Conductor Size In AWG/Kcmil 10 10 Reference: 1999 National Electrical Code (NEC) 1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse. 2 "Time-Delay" fuses are UL class "RK5" . 3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and above). Y Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. 2-12. Selecting A Location And Connecting Input Power 18 in (457 mm) of space for airflow Y Do not move or operate unit where it could tip. Y Always connect grounding conductor first. = GND/PE 1 Rating Label Supply correct input power. 2 Plug 3 Receptacle Connect plug to receptacle. 4 Input And Grounding Conductors Connect directly to line disconnect device if hard wiring is required. 5 Line Disconnect Device See Section 2-11. Y Special installation may be 5 required where gasoline or volatile liquids are present - see NEC Article 511 or CEC L1 Section 20. L2 1 1 2 4 3 L2 L1 230 VAC, 1 Ref. 801 568 / Ref. 800 797-C OM-194 199 Page 10