CyberPower PR1000RT2UC User Manual - Page 14

Menu / Test, Menu / Logs, Menu / Advanced Setup

Page 14 highlights

LCD OPERATION GUIDE (continued) Menu / Test This menu provides basic tests for users to check the current performance of the UPS. Item Self Test Alarm Test Default No Short Test Option  Yes  No  Short Test  Continuous Test Description Select Yes to order the UPS to quickly test the backup function by entering to battery mode, checking if it works. The test takes around 10 seconds. This item tests the alarm's audible warning and LED indicators' functionalities. Short test lasts 5 seconds. In continuous testing, press any button to stop the test. Menu / Logs All kinds of events are recorded and the UPS will show the last 10 events in this menu. Events are categorized into four sorts and shown in a capital letter in a single event log on the display screen: (F) Fault, (W) Warning, (S) Shutdown, and no letter for a normal transfer event. Menu / Advanced Setup This menu contains more adjustable and detailed items for UPS advanced usage. Read the item descriptions below thoroughly before you change the settings. Item Output Voltage Minimum Output Voltage Maximum Output Voltage Low Battery Threshold Default  120V*  *Select models and regions   100V: 89V  110V: 97V  120V: 102V  127V: 111V  100V: 111V  110V: 128V  120V: 131V  127V: 143V  300 seconds  Option 100V 110V 120V 127V 100V: 86-92V 110V: 97-106V 120V: 97-106V 127V: 108-114V 100V: 108-114V 110V: 127-136V 120V: 127-136V 127V: 140-146V 0-1800 seconds 35%  20-65% Description Select the AC output voltage on battery mode. Set the value lower if the utility voltage is usually low to avoid unnecessary battery usage. Make sure the connected equipment can work under the voltage condition. Set the value higher if the utility voltage is usually high to avoid unnecessary battery usage. Make sure the connected equipment can work under the voltage condition. The UPS will emit an audible alarm indicating that the remaining runtime is reaching its threshold. The UPS will emit an audible alarm indicating that the remaining battery capacity is reaching its threshold. 13

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27

13
Menu / Test
This menu provides basic tests for users to check the current performance of the UPS.
Item
Default
Option
Description
Self Test
No
Yes
No
Select Yes to order the UPS to quickly test the
backup function by entering to battery mode,
checking if it works. The test takes around 10
seconds.
Alarm Test
Short Test
Short Test
Continuous Test
This item tests the alarm’s audible warning and
LED indicators’ functionalities. Short test lasts 5
seconds. In continuous testing, press any button
to stop the test.
Menu / Logs
All kinds of events are recorded and the UPS will show the last 10 events in this menu. Events are categorized into four sorts and
shown in a capital letter in a single event log on the display screen: (F) Fault, (W) Warning, (S) Shutdown, and no letter for a normal
transfer event.
Menu / Advanced Setup
This menu contains more adjustable and detailed items for UPS advanced usage. Read the item descriptions below thoroughly before
you change the settings.
Item
Default
Option
Description
Output Voltage
120V*
*Select models and
regions
100V
110V
120V
127V
Select the AC output voltage on battery mode.
Minimum Output
Voltage
100V: 89V
110V: 97V
120V: 102V
127V: 111V
100V: 86-92V
110V: 97-106V
120V: 97-106V
127V: 108-114V
Set the value lower if the utility voltage is usually
low to avoid unnecessary battery usage.
Make sure the connected equipment can work
under the voltage condition.
Maximum Output
Voltage
100V: 111V
110V: 128V
120V: 131V
127V: 143V
100V: 108-114V
110V: 127-136V
120V: 127-136V
127V: 140-146V
Set the value higher if the utility voltage is usually
high to avoid unnecessary battery usage.
Make sure the connected equipment can work
under the voltage condition.
Low Battery
Threshold
300 seconds
0-1800 seconds
The UPS will emit an audible alarm indicating that
the remaining runtime is reaching its threshold.
35%
20-65%
The UPS will emit an audible alarm indicating that
the remaining battery capacity is reaching its
threshold.
LCD OPERATION GUIDE (continued)