CyberPower PR1000RT2UC User Manual - Page 18
Dry Contact
View all CyberPower PR1000RT2UC manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 18 highlights
DRY CONTACT This UPS offers users the solution for UPS status monitoring via two output relays. Refer to Network Operation in this manual, verifying the UPS is connected to a computer with PowerPanel Business software installed or is equipped with RMCARD. Follow below circuit to wire your dry contact port and choose your preferred monitoring status via those interfaces. UPS status which can be monitored by dry contact is listed below: UPS Status UPS Conditions Power Failure* UPS detects utility failure. Battery Low* Battery capacity is lower than threshold. Summary Alarm UPS exits alarms due to Inverter Fault, Output Short, Over Temperature, Overload, Battery Overcharge, Low Battery, Battery Disconnected, and Battery Defect. UPS Fail UPS has malfunctioned due to Inverter Fault, DC Power Fault, and Over Temperature. *Default settings of relay contacts are Power Failure and Battery Low (Normally Open). Internal Circuit Relay 1 Battery Low Common (for relays) 1 6 2 7 Relay 2 3 8 Power Failure 4 9 5 Output Relay Rating Voltage: 30VDC Max Current: 3A Max (per relay) Relay Status Pin1 short to Pin5 Pin8 short to Pin5 UPS Status Battery Low Power Failure Example Application Supply 12VDC to the Common contact and connect LEDs to the DB9 port Pin1 and Pin8. When UPS detects utility failure or when UPS battery capacity is lower than threshold, the connected LEDs will illuminate. Battery Low 1 6 2 7 12V 3 8 Power Failure 4 Common (for relays) 9 5 17