Dell PowerEdge MX7000 EMC PowerEdge MX7000 Enclosure Installation and Service - Page 58

Expanded operating range, Expanded operating temperature restrictions

Page 58 highlights

Table 34. Expanded operating temperature specifications(continued) Expanded operating temperature Specifications For temperatures between 40°C and 45°C, derate maximum allowable temperature by 1°C per 125 m (1°F per 228 ft) above 950 m (3.117 ft). NOTE: When operating in the expanded temperature range, the performance of the system may be impacted. NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD panel and in the System Event Log. Expanded operating range • The operating temperature is specified for a maximum altitude of 950 m for expanded operating range. • Do not perform cold start at 5°C or lower, due to hard drive constraints. • Redundant power supplies are required. Expanded operating temperature restrictions For more information about the expanded operating temperature restrictions, see the Installation and Service Manual for the PowerEdge MX sleds at www.dell.com/poweredgemanuals. Table 35. Expanded operating temperature restrictions System C30 Dell EMC PowerEdge MX7000 No restrictions including the fans, Management Module, and PSUs C35 No restrictions C40E45 No restrictions Fabrics A and B modules No restrictions No restrictions The MX9116n is not supported. Fabric C I/O modules No restrictions No restrictions No restrictions Particulate and gaseous contamination specifications The following table defines the limitations that help avoid any damages to the IT equipment and/or failure from particulates and gaseous contamination: If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer. Table 36. Particulate contamination specifications Particulate contamination Specifications Air Filtration Data center air filtration defines that, ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE: This condition applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. NOTE: Air entering the data center must have MERV11 or MERV13 filtration. Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies to data center and nondata center environments. Corrosive dust • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and nondata center environments. 58 Technical specifications

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63

Table 34. Expanded operating temperature specifications(continued)
Expanded operating
temperature
Specifications
For temperatures between 40°C and 45°C, derate maximum allowable temperature by 1°C per 125 m
(1°F per 228 ft) above 950 m (3.117 ft).
NOTE:
When operating in the expanded temperature range, the performance of the system may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD
panel and in the System Event Log.
Expanded operating range
The operating temperature is specified for a maximum altitude of 950 m for expanded operating range.
Do not perform cold start at 5°C or lower, due to hard drive constraints.
Redundant power supplies are required.
Expanded operating temperature restrictions
For more information about the expanded operating temperature restrictions, see the Installation and Service Manual for the PowerEdge
MX sleds at
www.dell.com/poweredgemanuals
.
Table 35. Expanded operating temperature restrictions
System
C30
C35
C40E45
Dell EMC PowerEdge MX7000
including the fans, Management
Module, and PSUs
No restrictions
No restrictions
No restrictions
Fabrics A and B modules
No restrictions
No restrictions
The MX9116n is not supported.
Fabric C I/O modules
No restrictions
No restrictions
No restrictions
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any damages to the IT equipment and/or failure from particulates and gaseous
contamination: If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure,
you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 36. Particulate contamination specifications
Particulate
contamination
Specifications
Air Filtration
Data center air filtration defines that, ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE:
This condition applies to data center environments only. Air filtration requirements do
not apply to IT equipment designed to be used outside a data center, in environments such as
an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE:
This condition applies to data center and nondata center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE:
This condition applies to data center and nondata center environments.
58
Technical specifications