Dell PowerEdge R650 EMC Technical Specifications - Page 15

Table 18. Maximum vibration specifications, Table 17. Shared requirements across all categories

Page 15 highlights

Table 14. Operational climatic range category A2 (continued) Temperature Specifications Temperature ranges for altitudes

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21

Table 14. Operational climatic range category A2 (continued)
Temperature
Specifications
Temperature ranges for altitudes <= 900 m (<=
2953 ft)
10–35°C (50–95°F) with no direct sunlight on the equipment
Humidity percent ranges (non-condensing at all
times)
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F)
maximum dew point
Operational altitude de-rating
Maximum temperature is reduced by 1°C/300 m (33.8°F/984 Ft) above
900 m (2953 Ft)
Table 15. Operational climatic range category A3
Temperature
Specifications
Allowable continuous operations
Temperature ranges for altitudes <= 900 m (<=
2953 ft)
5–40°C (41–104°F) with no direct sunlight on the equipment
Humidity percent ranges (non-condensing at all
times)
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating
Maximum temperature is reduced by 1°C/175 m (33.8°F/574 Ft) above
900 m (2953 Ft)
Table 16. Operational climatic range category A4
Temperature
Specifications
Allowable continuous operations
Temperature ranges for altitudes <= 900 m (<=
2953 ft)
5–45°C (41–113°F) with no direct sunlight on the equipment
Humidity percent ranges (non-condensing at all
times)
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating
Maximum temperature is reduced by 1°C/125 m (33.8°F/410 Ft) above
900 m (2953 Ft)
Table 17. Shared requirements across all categories
Temperature
Specifications
Allowable continuous operations
Maximum temperature gradient (applies to both
operation and non-operation)
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes (41°F in 15
minutes), 5°C in an hour* (41°F in an hour) for tape
NOTE:
* - Per ASHRAE thermal guidelines for tape hardware, these are
not instantaneous rates of temperature change.
Non-operational temperature limits
-40 to 65°C (-104 to 149°F)
Non-operational humidity limits
5% to 95% RH with 27°C (80.6°F) maximum dew point
Maximum non-operational altitude
12,000 meters (39,370 feet)
Maximum operational altitude
3,048 meters (10,000 feet)
Table 18. Maximum vibration specifications
Maximum vibration
Specifications
Operating
0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations)
Storage
1.88 G
rms
at 10 Hz to 500 Hz for 15 minutes (all six sides tested)
Technical specifications