Dell PowerEdge T140 EMC Technical Specifications - Page 13

Particulate and gaseous contamination specifications, Thermal restriction matrix

Page 13 highlights

• The operating temperature specified is for a maximum altitude of 3048 m (10,000 ft). • One non-redundant power supply unit is required. • One system fan required. • Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported. • GPU is not supported. • Tape backup unit is not supported. • For a system with 4 TB (or more) drive capacity, PERC is required for thermal control. Particulate and gaseous contamination specifications The following table defines the limitations that help avoid any damages to the IT equipment and/or, or both failure from particulate and gaseous contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and results in equipment damage or failure, you must rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer. Table 19. Particulate contamination specifications Particulate contamination Air filtration Specifications Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE: This condition applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. NOTE: Air entering the data center must have MERV11 or MERV13 filtration. Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE: This condition applies to data center and nondata center environments. Corrosive dust • Air must be free of corrosive dust. • Residual dust present in the air must have a deliquescent point less than 60% relative humidity. NOTE: This condition applies to data center and nondata center environments. Table 20. Gaseous contamination specifications Gaseous contamination Copper Coupon Corrosion Silver Coupon Corrosion Specifications

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

The operating temperature specified is for a maximum altitude of 3048 m (10,000 ft).
One non-redundant power supply unit is required.
One system fan required.
Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
GPU is not supported.
Tape backup unit is not supported.
For a system with 4 TB (or more) drive capacity, PERC is required for thermal control.
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any damages to the IT equipment and/or, or both failure from particulate and
gaseous contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and results in equipment damage or
failure, you must rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 19. Particulate contamination specifications
Particulate contamination
Specifications
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit.
NOTE:
This condition applies to data center
environments only. Air filtration requirements do not
apply to IT equipment designed to be used outside a
data center, in environments such as an office or factory
floor.
NOTE:
Air entering the data center must have MERV11
or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-
data center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point
less than 60% relative humidity.
NOTE:
This condition applies to data center and non-
data center environments.
Table 20. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper Coupon Corrosion
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Silver Coupon Corrosion
<200 Å/month as defined by AHSRAE TC9.9.
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Thermal restriction matrix
Table 21. Thermal restrictions matrix
Ambient
25°C
30°C
35°C
Processor
No restriction
No restriction
No restriction
DIMM
No restriction
No restriction
No restriction
Technical specifications