Fluke 87V FE 83V & 87V Users Manual - Page 34
Fluke 87V Manual
View all Fluke 87V manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 34 highlights
80 Series V Users Manual 3. If you are using the A terminal, set the rotary switch to mA/A. If you are using the mA/µA terminal, set the rotary switch to µA for currents below 6000 µA (6 mA), or mA/A for currents above 6000 µA. 4. To measure dc current, press A. 5. Break the circuit path to be tested. Touch the black probe to the more negative side of the break; touch the red probe to the more positive side of the break. Reversing the leads will produce a negative reading, but will not damage the Meter. 6. Turn on power to the circuit; then read the display. Be sure to note the unit given at the right side of the display (µA, mA, or A). 7. Turn off power to the circuit and discharge all highvoltage capacitors. Remove the Meter and restore the circuit to normal operation. The following are some tips for measuring current: • If the current reading is 0 and you are sure the Meter is set up correctly, test the Meter's fuses as described under "Testing the Fuses". • A current Meter drops a small voltage across itself, which might affect circuit operation. You can calculate this burden voltage using the values listed in the specifications in Table 14. 26