GE 60-774 Installation Instructions - Page 4

Wiring the Module - com

Page 4 highlights

Wiring the Module Wiring the Module To Wire the Module to a Panel To Wire Detectors to the Module Follow the maximum zone input wire length (run) guidelines in Table 5 based on the type of wire used. t On Advent panels, the BUS 1 and BUS 2 headers must be used only for fire or burglary applications. Do not mix fire and burglary bus devices on either header. 1. Make sure the panel AC power is turned off or removed, and the panel backup battery(s) are disconnected. 2. Wire the module to the panel as shown in Figure 7 and explained in Table 4. t For Advent UL-864 Listed Installations, all inputs must be dedicated to either fire or burglary applications. Do not mix fire and burglary on any module in any partition for these installations. Table 5. Zone Input Wire Runs Gauge Max. Wire Run* 18 750 Feet 22 300 Feet *Wire run based on 10 ohms maximum wire and device resistance including 2.0K ohm EOL resistor. 1. Figure 8 shows an example of how to connect up to eight normally closed (N/C) or normally open (N/O) intrusion circuits to the module. ZONE COM ZONE 1 GND (BLK) BUS B (WHT) BUS A (GRN) +12 VDC (RED) ZONE 8 ZONE COMMON ZONE 7 ZONE 6 ZONE COMMON ZONE 5 ZONE 4 ZONE COMMON ZONE 3 ZONE 2 ZONE COMMON ZONE 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TO PANEL TO ZONE SUPERBUS TERMINALS INPUT OR CONNECTOR DEVICE (SEE TABLE) (SHARED COMMONS) 9712G03A.DSF Figure 7. General Module Wiring Table 4. SuperBus Module/Panel Wiring Module Advent* Terminals UltraGard 13 Red 12 (+12VDC) 14 (BUS A) Green 13 15 (BUS B) White 14 16 (GND) Black 15 Concord 4 5 6 3 * Panel SuperBus device connector wiring harness. (Connect to either panel connector.) 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 UL-LISTED NORMALLY CLOSED (N/C) CONTACTS IN SERIES < OR > UL-LISTED NORMALLY OPEN (N/O) CONTACTS IN PARALLEL 2.0K OHM EOL RESISTOR 49-467 (INSTALL AT LAST DEVICE) 9712G04A.DSF Figure 8. Connecting N/C and N/O Intrusion Circuits to the Module

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8

4
Wiring the Module
Wiring the Module
To Wire the Module to a Panel
On Advent panels, the BUS 1 and BUS 2 headers
must be used only for fire or burglary applications. Do
not mix fire and burglary bus devices on either header.
1.
Make sure the panel AC power is turned off or
removed, and the panel backup battery(s) are
disconnected.
2.
Wire the module to the panel as shown in Figure 7 and
explained in Table 4.
Figure 7.
General Module Wiring
* Panel SuperBus device connector wiring harness.
(Connect to either panel connector.)
To Wire Detectors to the Module
Follow the maximum zone input wire length (run)
guidelines in Table 5 based on the type of wire used.
For Advent UL-864 Listed Installations, all inputs must
be dedicated to either fire or burglary applications. Do
not mix fire and burglary on
any
module in
any
partition for these installations.
1.
Figure 8 shows an example of how to connect up to
eight normally closed (N/C) or normally open (N/O)
intrusion circuits to the module.
Figure 8.
Connecting N/C and N/O Intrusion Circuits
to the Module
Table 4. SuperBus Module/Panel Wiring
Module
Terminals
Advent*
Ultra-
Gard
Concord
13
(+12VDC)
Red
12
4
14 (BUS A)
Green
13
5
15 (BUS B)
White
14
6
16 (GND)
Black
15
3
9712G03A.DSF
1234
5
6
7
8 9 10 11 12 13 14 15 16
ZONE COMMON
ZONE 1
ZONE 2
+12 VDC (RED)
BUS A (GRN)
BUS B (WHT)
GND (BLK)
TO PANEL
SUPERBUS TERMINALS
OR CONNECTOR
(SEE TABLE)
TO ZONE
INPUT
DEVICE
(SHARED COMMONS)
ZONE 3
ZONE 4
ZONE 5
ZONE COMMON
ZONE COMMON
ZONE 6
ZONE 7
ZONE COMMON
ZONE 8
Table 5. Zone Input Wire Runs
Gauge
Max. Wire Run*
18
750 Feet
22
300 Feet
*Wire run based on 10 ohms maximum wire and
device resistance including 2.0K ohm EOL resistor.
9712G04A.DSF
1234
5
6
7
8 9 10 1112 1314 15 16
ZONE 1
ZONE COM
UL-LISTED
NORMALLY
OPEN
(N/O)
CONTACTS
IN PARALLEL
2.0K OHM EOL RESISTOR 49-467
(INSTALL AT LAST DEVICE)
UL-LISTED
NORMALLY
CLOSED
(N/C)
CONTACTS
IN SERIES
< OR >