Installation Instructions 265 VOLT ELECTRICAL CONNECTION OPTIONS WARNING: Connection of this 265 V AC product to a branch circuit MUSTbe done by direct connection in accordance with the National ElectricalCode. Plugging this unit into a building-mounted exposed receptacle is not permitted by code. These models must be installed using the appropriate GEpower supply kit for the branch circuit amperage and the electrical resistance heater wattage desired. Use the POWERCONNECTIONCHARTon page 16 to determine the correct kit required. One of the following installation methods (A or B) must be used. A. FOR SUBBASE INSTALLATION Electrical subbase kits are available to provide a flexible enclosure for direct connection. Branch Circuit and Unit Amperage Rating 15 20 30 Proper GE Subbase Kit RAK204E15 RAK204E20 RAK204E30 Power Supply Kit RAK5172 RAK5202 RAK5302* *Not approved for use on 7000 BTUmodels. The instructions provided with the selected subbase kit must be carefully followed. It isthe responsibility of the installer to ensure the connection of components is done in accordance with these instructions and all electrical codes. B. FOR DIRECTCONNECT INSTALLATION If an electrical subbase is not used, direct connection to branch circuit wiring inside the provided junction box must be done in accordance with the following steps. Order the following Kit for 265-volt direct connection as required: Branch Circuit and Unit Amperage Rating 15 Power Supply Kit RAK5157 20 RAK5207 :30 RAK5307* *Not approved for use on 7000 BTUmodels. Proceed to the "MAKE ELECTRICALCONNECTION TO THE UNIT" section. I NOTE: Order Kit RAK4002CW to enable a quick disconnect inside the junction box. I 14

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

Installation
Instructions
265 VOLT ELECTRICAL CONNECTION
OPTIONS
WARNING:
Connection of this 265 V AC product to a branch circuit
MUSTbe done by direct connection in accordance with
the National ElectricalCode. Plugging this unit into a
building-mounted exposed receptacle is not permitted
by code.
These models must be installed using the appropriate
GEpower supply kit for the branch circuit amperage and
the electrical resistance heater wattage desired. Use the
POWERCONNECTIONCHARTonpage16to determine
the correct kit required. One of the following installation
methods (A or B) must be used.
A.
FOR SUBBASE INSTALLATION
Electrical subbase kits are
available
to provide a flexible
enclosure for direct connection.
Branch
Circuit
and
Proper
GE
Power
Unit Amperage
Rating
Subbase
Kit
Supply
Kit
15
RAK204E15
RAK5172
20
RAK204E20
RAK5202
30
RAK204E30
RAK5302*
*Not approved for use on 7000 BTUmodels.
The instructions provided with the selected subbase kit
must be carefully followed. It isthe responsibility of the
installer to ensure the connection of components is done
in accordance with these instructions and all electrical
codes.
I
B. FOR DIRECTCONNECT
INSTALLATION
If an electrical subbase is not used, direct connection to
branch circuit wiring inside the provided junction box must
be done in accordance with the following steps.
Order the following Kit for 265-volt direct connection
as required:
Branch
Circuit
and
Power
Unit Amperage
Rating
Supply
Kit
15
RAK5157
20
RAK5207
:30
RAK5307*
*Not approved for use on 7000 BTUmodels.
Proceed to the "MAKE ELECTRICALCONNECTION TO THE
UNIT" section.
NOTE: Order Kit RAK4002CW to enable a quick
disconnect inside the junction
box.
I