Hayward Pro Logic Model: PL-P-4 Installation - Page 18

Pro Logic Output, VSP Address - control board

Page 18 highlights

Pentair/Purex/MiniMax 1. Turn power off to heater. 2. Remove factory installed jumper from the "Ext Switch" connector. 3. Wire the Pro Logic to the "Ext Switch" connector as shown below. 4. The wires to the Pro Logic must be separated from any line voltage wires. Failure to follow these instructions may cause erratic operation of the heater. 5. Set the Power (Thermostat Select) switch to either "Pool" or "Spa". 6. Set the "Pool" and "Spa" thermostats to their maximum settings. Remove Factory Jumper Ext. Switch MINIMAX Raypak RP2100 Pool/Spa Heater 1. Turn power off to heater. 2. Push the mode button to "spa" mode. 3. Set the temperature to the maximum. 4. Push the mode button to "OFF". 5. Lastly, plug the prewired connector in the P7 position on the board. ! IMPORTANT: The heater will display "OFF" when it is being remotely controlled by the Pro Logic. Some homeowners see the "OFF" display and, thinking this is a mistake, change the mode to "POOL" or "SPA" which then disables the remote control by the Pro Logic. To prevent this: Remove the heater touch pad connector (P5) which will disable the touchpad. Black Orange Stripe Orange Black Stripe Light Blue P7 Drawing is for digital heater. If heater is a millivolt (analog), run red wires from Fireman's Switch to heater relay. RAYPAK RP2100 15 STA-RITE Heater 1. Turn power off to heater. 2. Remove upper jacket and open the control box. 3. Remove the jumper for the "fireman's switch. 4. Wire to the Pro Logic using wire rated for 105°C minimum. Fireman's Switch Operating 'Control Terminal Board STA-RITE Hayward Variable Speed Pump (VSP) Wiring and Address Setting Refer to your TriStar or EcoStar manual(s) for proper low voltage communication wiring between the Pro Logic and the Hayward Variable Speed Pump. A pump address must be configured for each VSP used in the system. This address is entered into the VSP's configuration menu. Refer to the table below to determine which address to use for your specific pump and Pro Logic. Select the proper address based on which output will be used and the model VSP you are configuring. Pro Logic Output This is the output used to control the VSP. Note that the VSP should be wired to this output's corresponding relay. FILTER AUX1 LIGHTS VSP Address This is the name that should be selected under "Set COMM bus address" (EcoStar) or "*H.Comm ADDR." (TriStar) within the VSP's Configuration Menu. "001" - Tristar "Pool Filter" - EcoStar "002" - Tristar "Aux1 / Spa Filter" - EcoStar "Lights Button" - EcoStar only AUX2 Aux2 - EcoStar only 16

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18

Pentair/Purex/MiniMax
1.
Turn power off to heater.
2.
Remove factory installed jumper from the “Ext Switch” connector.
3.
Wire the Pro Logic to the “Ext Switch” connector as shown below.
4.
The wires to the Pro Logic must be separated from any line voltage wires.
Failure to follow these instructions
may cause erratic operation of the heater.
5.
Set the Power (Thermostat Select) switch to either “Pool” or “Spa”.
6.
Set the “Pool” and “Spa” thermostats to their maximum settings.
MINIMAX
Ext.
Switch
Remove
Factory Jumper
Raypak RP2100 Pool/Spa Heater
1.
Turn power off to heater.
2.
Push the mode button to “spa” mode.
3.
Set the temperature to the maximum.
4.
Push the mode button to “OFF”.
5.
Lastly, plug the
prewired connector in the P7 position on the board.
!
IMPORTANT:
The heater will display “OFF” when it is being remotely controlled by the Pro Logic.
Some homeowners see the “OFF” display and, thinking this is a mistake, change the mode to “POOL” or
“SPA” which then disables the remote control by the Pro Logic.
To prevent this:
Remove the heater touch
pad connector (P5) which will disable the touchpad.
P7
Light Blue
Black
Orange Stripe
Orange
Stripe
Black
RAYPAK RP2100
Drawing is for digital
heater. If heater is a
millivolt (analog),
run red wires from
Fireman’s Switch
to heater relay.
15
ST
A-RITE Heater
1.
Turn power off to heater.
2.
Remove upper jacket and open the control box.
3.
Remove the jumper for the “fireman’s switch.
4.
Wire to the Pro Logic using wire rated for 105°C minimum.
STA-RITE
Terminal
Board
Operating
‘Control
Fireman’s
Switch
Hayward Variable Speed Pump (VSP) Wiring and Address Setting
Refer to your TriStar or EcoStar manual(s) for proper low voltage communication wiring between the Pro Logic and
the Hayward Variable Speed Pump.
A pump address must be configured for each VSP used in the system.
This address is entered into the VSP’s
configuration menu.
Refer to the table below to determine which address to use for your specific pump and Pro Logic.
Select the proper address based on which output will be used and the model VSP you are configuring.
16
FILTER
AUX1
A
2
UX
LIGHTS
Pro Logic Output
This is the output used to control the VSP.
Note that the VSP should be wired to this
output’s corresponding relay.
VSP Address
This is the name that should be selected
under “Set COMM bus address” (EcoStar)
or “*H.Comm ADDR.” (TriStar) within the
VSP’s Configuration Menu.
“001” - Tristar
“Pool Filter” - EcoStar
“002” - Tristar
” - EcoStar
Aux1 / Spa Filter
“Lights Button” - EcoStar only
Aux2 - EcoStar only