top and tighten.

Page 15 highlights

4. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the cable access panel and tighten. From the system chassis rail to the rack top: 1. Insert a T-25 Torx screw through on end of a 15.24-cm (6-in) grounding strap and secure it to the system chassis rail. 2. Place the other end of the same grounding strap over the grounding lug on the rack top. 3. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding strap on the rack top and tighten. From the grounding lug on the rack top to the grounding lug on the perforated panel: 1. Place one end of a 36.83-cm (14.5-in) grounding strap over the same grounding strap on the rack top. 2. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the rack top and tighten. 3. Place the other end of the same grounding strap over the grounding lug on the perforated panel. Installing the HP Ground Bonding Rack Option Kit 15

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19

Installing the HP Ground Bonding Rack
Option Kit 15
4.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the cable
access panel and tighten.
From the system chassis rail to the rack top:
1.
Insert a T-25 Torx screw through on end of a 15.24-cm (6-in) grounding strap and secure it to the
system chassis rail.
2.
Place the other end of the same grounding strap over the grounding lug on the rack top.
3.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding strap on the rack
top and tighten.
From the grounding lug on the rack top to the grounding lug on the perforated panel:
1.
Place one end of a 36.83-cm (14.5-in) grounding strap over the same grounding strap on the rack
top.
2.
Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the rack
top and tighten.
3.
Place the other end of the same grounding strap over the grounding lug on the perforated panel.