2. Place the other end of the same grounding strap over the grounding lug on the right rear door. 3. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the right rear door and tighten. From the system chassis rail to the left rear door: 1. Insert a T-25 Torx screw through the end of a 36.83-cm (14.5-in) grounding strap, and secure it to the system chassis rail. 2. Place the other end of the grounding strap over the grounding lug on the left rear door. 3. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the left rear door and tighten. From the left rear door to the left rear door cable access panel: 1. Place one end of a 15.24-cm (6-in) grounding strap over the grounding lug on the left rear door. 2. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the left rear door and tighten. 3. Place the other end of the same grounding strap over the grounding lug on the cable access panel. Installing the HP Ground Bonding Rack Option Kit 6