HP Integrity rx4640 Site Preparation Guide, Second Edition - HP Integrity rx46 - Page 12

Dimensions and Weights, Component Dimensions, Grounding, Electrical Specifications, Circuit Breaker

Page 12 highlights

System Specifications Dimensions and Weights Dimensions and Weights This section provides dimensions and weights of hp Integrity rx4640 server components. Component Dimensions Table 1-2 Rack Mounted Server Component Dimensions Dimension Height- Centimeters (Inches) Width- Centimeters (Inches) Depth- Centimeters (Inches) Weight- Kilograms (Pounds) Value 17.3 cm (6.8 in.) 48.2 cm (19 in.) 69.0 cm (27.2 in.) Unloaded 40 kg (88 lb.) Fully loaded 45.4 kg (100 lb.) Grounding The site building shall provide a safety ground/protective earth for each AC service entrance to all cabinets. Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing conductor is to be connected from the unit to the building installation earth or, if supplied by a separately derived system, at the supply transformer or motor-generator set grounding point. Electrical Specifications This section provides electrical specifications for the system. Circuit Breaker The marked electrical for the HP Server is 8 amps. The recommended circuit breaker size is 12 amps per line cord (2 maximum) for North America. For countries outside North America, consult the local electrical authority that has jurisdiction for the recommended circuit breaker size. 12 Chapter 1

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49

System Specifications
Dimensions and Weights
Chapter 1
12
Dimensions and Weights
This section provides dimensions and weights of hp Integrity rx4640 server components.
Component Dimensions
Grounding
The site building shall provide a safety ground/protective earth for each AC service entrance to all cabinets.
Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the
branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing
conductor is to be connected from the unit to the building installation earth or, if supplied by a separately
derived system, at the supply transformer or motor-generator set grounding point.
Electrical Specifications
This section provides electrical specifications for the system.
Circuit Breaker
The marked electrical for the HP Server is 8 amps. The recommended circuit breaker size is 12 amps per line
cord (2 maximum) for North America. For countries outside North America, consult the local electrical
authority that has jurisdiction for the recommended circuit breaker size.
Table 1-2
Rack Mounted Server Component Dimensions
Dimension
Value
Height- Centimeters (Inches)
17.3 cm (6.8 in.)
Width- Centimeters (Inches)
48.2 cm (19 in.)
Depth- Centimeters (Inches)
69.0 cm (27.2 in.)
Weight- Kilograms (Pounds)
Unloaded 40 kg (88 lb.)
Fully loaded 45.4 kg (100 lb.)