System Specifications Electrical Specifications Typical System Configurations The system configurations shown in Table 1-6, Typical Configuration Power Consumption Values, are typical of most systems and show the power and cooling values required for the listed components. These power and cooling values are considered typical and not maximum for the configurations shown. Table 1-6 Typical Configuration Power Consumption Values CPU Qty Memory Gigabytes 1 1 GB PCI Cards (assuming 10W each) DVDs Hard Disk Drives 0 0 1 Core I/O 2 Bulk Power Supplies Typical PowerWatts Typical CoolingBTU/Hr 2 410 1399.74 (4 DIMMs @ 256 MB ea.) 2 32 GBa 0 0 1 1 1 540 1843.56 (32 DIMMs @ 1 GB ea.) 2 32 GBa 6 1 2 2 2 700 2389.80 (32 DIMMs @ 1 GB ea.) 4 32 GBa 0 1 2 2 2 895 3055.53 (32 DIMMs @ 1 GB ea.) 4 32 GBa 6 1 2 2 2 975 3328.65 (32 DIMMs @ 1 GB ea.) 4 64 GBa 6 1 2 2 2 1050 3584.70 (32 DIMMs @ 2GB ea.) a. These memory configurations require the optional 32 DIMM slot memory extender board. The standard memory extender board has 16 DIMM slots. Chapter 1 15