HP Integrity rx8640 Site Preparation Guide, Fourth Edition - HP Integrity rx86 - Page 35

Circuit Breaker, System AC Power Specifications, Power Cords

Page 35 highlights

Install a protective earthing (PE) conductor that is identical in size, insulation material, and thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing conductor described is to be connected from the unit to the building installation earth or if supplied by a separately derived system, at the supply transformer or motor-generator set grounding point. Circuit Breaker The Marked Electrical for the server is 15 amps per line cord. The recommended circuit breaker size is 20 amps for North America. For countries outside North America, consult your local electrical authority having jurisdiction for the recommended circuit breaker size. The server contains four C20 power receptacles located at the bottom rear bulkhead. A minimum of two power cords (A0-A1) must be used to maintain normal operation of the server. A second set of two cords (B0-B1) can be added to improve system availability by protecting, for example, against power source failures or accidentally tripped circuit breakers. The server can receive AC input from two different AC power sources. System AC Power Specifications Power Cords Table 2-5 lists the various power cables available for use with the server. Each power cord is 15 feet (4.5-m) in length with a IEC 60320-1 C19 female connector attached to one end. Table 2-5 Power Cords Part Number 8120-6895 8120-6897 8121-0070 8120-6903 Description Stripped end, 240 volt Male IEC309, 240 volt Male GB-1002, 240 volt Male NEMA L6-20, 240 volt Where Used International - Other International China North America/Japan System Power Specifications Table 2-6 lists the AC power requirements for the servers. This table provides information to help determine the amount of AC power needed for your computer room. Table 2-6 HP Integrity rx8640 and HP 9000 rp8440 AC Power Requirements Requirements Value Nominal input voltage 200-240 VAC Minimum operating voltage 180 VAC Maximum operating voltage 269 VAC Frequency range (minimum - maximum) 50/60 Hz Number of phases 1 Rated line current 15 A Maximum inrush current 54 A peak for 20 ms Dropout carry-through time at minimum 20 ms line voltage Circuit breaker rating 20A Comments Per line cord Per line cord Per line cord Electrical Specifications 35

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45

Install a protective earthing (PE) conductor that is identical in size, insulation material, and
thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow
stripes. The earthing conductor described is to be connected from the unit to the building
installation earth or if supplied by a separately derived system, at the supply transformer or
motor-generator set grounding point.
Circuit Breaker
The Marked Electrical for the server is 15 amps per line cord. The recommended circuit breaker
size is 20 amps for North America. For countries outside North America, consult your local
electrical authority having jurisdiction for the recommended circuit breaker size.
The server contains four C20 power receptacles located at the bottom rear bulkhead. A minimum
of two power cords (A0–A1) must be used to maintain normal operation of the server. A second
set of two cords (B0–B1) can be added to improve system availability by protecting, for example,
against power source failures or accidentally tripped circuit breakers. The server can receive AC
input from two different AC power sources.
System AC Power Specifications
Power Cords
Table 2-5
lists the various power cables available for use with the server. Each power cord is 15
feet (4.5-m) in length with a IEC 60320-1 C19 female connector attached to one end.
Table 2-5 Power Cords
Where Used
Description
Part Number
International - Other
Stripped end, 240 volt
8120-6895
International
Male IEC309, 240 volt
8120-6897
China
Male GB-1002, 240 volt
8121-0070
North America/Japan
Male NEMA L6-20, 240 volt
8120-6903
System Power Specifications
Table 2-6
lists the AC power requirements for the servers. This table provides information to
help determine the amount of AC power needed for your computer room.
Table 2-6 HP Integrity rx8640 and HP 9000 rp8440 AC Power Requirements
Comments
Value
Requirements
200–240 VAC
Nominal input voltage
180 VAC
Minimum operating voltage
269 VAC
Maximum operating voltage
50/60 Hz
Frequency range (minimum - maximum)
1
Number of phases
Per line cord
15 A
Rated line current
Per line cord
54 A peak for 20 ms
Maximum inrush current
20 ms
Dropout carry-through time at minimum
line voltage
Per line cord
20A
Circuit breaker rating
Electrical Specifications
35