HP LH4r HP Netserver LH 4r Rack Cabling Guide - Page 24
Mounting the PDU Horizontally
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 24 highlights
Chapter 2 Connecting and Routing Cables to the HP NetServer LH 4r Figure 2-3. Mounting a Pair of PDUs Horizontally (Rear View) Once you have determined the general location and orientation, install the PDUs for the rack as described below: Mounting the PDU Horizontally Installation Steps To mount a PDU horizontally, follow these steps: 1. Determine the exact location of the PDU. A PDU is not recommended behind certain HP units, as shown in Table 2-2. (Horizontally mounted PDUs conflict with mechanical access if mounted behind these units.) A PDU can be located in an empty EIA unit and a filler panel put in the corresponding space in the rack front. 20
Chapter 2
Connecting and Routing Cables to the HP NetServer LH 4r
20
Figure 2-3. Mounting a Pair of PDUs Horizontally (Rear View)
Once you have determined the general location and orientation, install the PDUs
for the rack as described below:
Mounting the PDU Horizontally
Installation Steps
To mount a PDU horizontally, follow these steps:
1.
Determine the exact location of the PDU. A PDU is not recommended
behind certain HP units, as shown in Table 2-2. (Horizontally mounted
PDUs conflict with mechanical access if mounted behind these units.)
A PDU can be located in an empty EIA unit and a filler panel put in
the corresponding space in the rack front.