HP LH4r HP Netserver LH 4r Rack Cabling Guide - Page 36

PDU Rack Power Configurations

Page 36 highlights

Chapter 2 Connecting and Routing Cables to the HP NetServer LH 4r Two 120 V PDUs per UPS Possible Two 120 VAC PDUs can be plugged into the UPS in this 120 V power configuration. There are also six NEMA 5-15R receptacles in the standard UPS which can be used for equipment in the same rack if needed. 200/208V PDU Rack Power Configurations The 208 VAC PDU power configurations appear as shown below in Table 2-5 and Figure 2-9. Recommended 208 VAC Power Configurations In the United States, if you are using a UPS use PDU model E7671A or E7672A. Attach the IEC 320 C19 end of the E7801A cord to the PDU and attach the L6-20 end of the same cord to the NEMA L6-20 receptacle on the UPS. Alternate 208 VAC Power Configurations In the 208 VAC case, without a UPS, make sure your power system has the capacity to support the power and current needs of the components you will power (see the section titled "Site Preparation: Circuit Breakers "). If power and current capacity are adequate, plug the PDU into a 208 V, L6-20 receptacle. 32

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61

Chapter 2
Connecting and Routing Cables to the HP NetServer LH 4r
32
Two 120 V PDUs per UPS Possible
Two
120 VAC PDUs can be plugged into the UPS in this 120 V power
configuration. There are also six NEMA 5-15R receptacles in the standard UPS
which can be used for equipment in the same rack if needed.
200/208V
PDU Rack Power Configurations
The
208 VAC PDU power configurations appear as shown below in Table
2
-
5
and Figure
2
-
9.
Recommended 208 VAC Power Configurations
In the United States, if you are using a UPS use PDU model E7671A or E7672A.
Attach the IEC 320 C19 end of the E7801A cord to the
PDU and attach the
L6-20 end of the same cord to the NEMA L6-20 receptacle on the UPS.
Alternate 208 VAC Power Configurations
In the 208 VAC case, without a UPS, make sure your power system has the
capacity to support the power and current needs of the components you will
power (see the section titled
"
Site Preparation: Circuit Breakers
"
). If power and
current capacity are adequate, plug the
PDU into a 208 V, L6-20 receptacle.