HP LH4r HP Netserver LH 4r Rack Cabling Guide - Page 36
PDU Rack Power Configurations
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 36 highlights
Chapter 2 Connecting and Routing Cables to the HP NetServer LH 4r Two 120 V PDUs per UPS Possible Two 120 VAC PDUs can be plugged into the UPS in this 120 V power configuration. There are also six NEMA 5-15R receptacles in the standard UPS which can be used for equipment in the same rack if needed. 200/208V PDU Rack Power Configurations The 208 VAC PDU power configurations appear as shown below in Table 2-5 and Figure 2-9. Recommended 208 VAC Power Configurations In the United States, if you are using a UPS use PDU model E7671A or E7672A. Attach the IEC 320 C19 end of the E7801A cord to the PDU and attach the L6-20 end of the same cord to the NEMA L6-20 receptacle on the UPS. Alternate 208 VAC Power Configurations In the 208 VAC case, without a UPS, make sure your power system has the capacity to support the power and current needs of the components you will power (see the section titled "Site Preparation: Circuit Breakers "). If power and current capacity are adequate, plug the PDU into a 208 V, L6-20 receptacle. 32