Placement of PDU
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 21 highlights
Chapter 2 Connecting and Routing Cables to the HP NetServer LXr 8000 Placement of PDU To determine where the PDU mounts, eliminate positions directly behind equipment listed in Table 2-2. (PDUs conflict with these units when mounted in the same space). Then decide the most convenient location. The PDU can be mounted vertically using the non-EIA mounting holes on the outer edges of the vertical columns (except in the case of the LXr Pro8, where it mechanically conflicts). Or it can be mounted horizontally between the columns. Figures 2-3, 2-4, and 2-5 show possible PDU positions and orientations. The PDU is usually mounted horizontally across the rack opening but can be mounted vertically on the opposite side of the rack from the door hinges. Table 2-2. PDU Placement Is Not Recommended Behind These Units HP Product Name Can PDU Be Mounted Behind? Reason HP NetServer LXr 8000 HP NetServer LXr Pro8 HP NetServer LH 3r HP FiberChannel 30 HP NetServer Rack Storage/8 Horizontal Mounting Not Interferes with Hot- Recommended Swappable Power Supplies Neither Horizontal Nor Cannot Extend NetServer Vertical Mounting Possible Satellite for Servicing Horizontal Mounting Not Interferes with HotRecommended at Bottom of Swappable Power Supplies LH 3r Not Feasible Mechanically conflicts. Horizontal Mounting Not Interferes with Hot- Recommended Swappable Power Supplies 17