HP LH4r HP Netserver LXr 8000 Rack Cabling Guide - Page 33

IEC 320 C-19 plug. The 208 VAC

Page 33 highlights

Chapter 2 Connecting and Routing Cables to the HP NetServer LXr 8000 Table 2-3. 200/208 VAC Components Component (Note 1) Model Power (VA) Power (W) Current (A) Note 2 208 VAC PDU E7671A or E7672A N/A N/A maximu m 16 HP NetServer LXr D6021A (single 400 MHz 1,121 1,077 5.6 8000 processor, 512K Cache) D6022A (single 400 MHz processor, 1 MB Cache) HP NetServer Rack Storage/8 D4902A 211 209 1.1 HP Console Switch J1497A 42 29 0.2 Note 1 More ratings are listed in Table 3-4. For a full list of power ratings, see the rack configuration utilities (for instance, Rack Assistant) on the HP Web Site. Note 2 Indicated current ratings are for use in selecting PDU and UPS components and may not reflect actual measured amounts. Description of the Recommended 208 VAC Configuration Figure 2-8 shows a UPS connected to the power mains through a captive cord terminated with an L6-20P plug. The UPS has five receptacles for use in the rack: two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and one L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via a detachable cord with an L6-20P plug. This cord connects to the PDU with an IEC 320 C-19 plug. The 208 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13 receptacles. A second PDU (E7672A) is available, which can be daisychained to the 16-amp unit, providing ten more C-13 receptacles. The fan (not required if perforated doors--or no doors--are used front and back) plugs into one of the C-13 receptacles on the PDU. 29

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53

Chapter 2
Connecting and Routing Cables to the HP NetServer LXr 8000
29
Table 2-3. 200/208 VAC Components
Component
(Note 1)
Model
Power
(VA)
Power
(W)
Current
(A)
Note 2
208 VAC
PDU
E7671A or E7672A
N/A
N/A
maximu
m 16
HP NetServer LXr
8000
D6021A (single 400 MHz
processor, 512K Cache)
D6022A (single 400 MHz
processor, 1 MB Cache)
1,121
1,077
5.6
HP NetServer
Rack Storage/8
D4902A
211
209
1.1
HP Console Switch
J1497A
42
29
0.2
Note 1
More ratings are listed in Table 3-4. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2
Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 208 VAC Configuration
Figure 2
-
8 shows a UPS connected to the power mains through a captive cord
terminated with an L6-20P plug. The UPS has five receptacles for use in the
rack: two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and
one L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via a
detachable cord with an L6-20P plug. This cord connects to the
PDU with an
IEC 320 C-19 plug. The 208 VAC
PDU has two IEC 320, C-19 and six IEC 320,
C-13 receptacles. A second PDU (E7672A) is available, which can be daisy-
chained to the 16-amp unit, providing ten more C-13 receptacles. The fan (not
required if perforated doors--or no doors--are used front and back) plugs into one
of the C-13 receptacles on the PDU.