HP LH4r HP Netserver LXr 8000 Rack Cabling Guide - Page 33
IEC 320 C-19 plug. The 208 VAC
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 33 highlights
Chapter 2 Connecting and Routing Cables to the HP NetServer LXr 8000 Table 2-3. 200/208 VAC Components Component (Note 1) Model Power (VA) Power (W) Current (A) Note 2 208 VAC PDU E7671A or E7672A N/A N/A maximu m 16 HP NetServer LXr D6021A (single 400 MHz 1,121 1,077 5.6 8000 processor, 512K Cache) D6022A (single 400 MHz processor, 1 MB Cache) HP NetServer Rack Storage/8 D4902A 211 209 1.1 HP Console Switch J1497A 42 29 0.2 Note 1 More ratings are listed in Table 3-4. For a full list of power ratings, see the rack configuration utilities (for instance, Rack Assistant) on the HP Web Site. Note 2 Indicated current ratings are for use in selecting PDU and UPS components and may not reflect actual measured amounts. Description of the Recommended 208 VAC Configuration Figure 2-8 shows a UPS connected to the power mains through a captive cord terminated with an L6-20P plug. The UPS has five receptacles for use in the rack: two (on the right rear) NEMA 5-15 providing 110 VAC, two L6-20R, and one L6-30R, providing 208VAC. The E7671A PDU connects to the UPS via a detachable cord with an L6-20P plug. This cord connects to the PDU with an IEC 320 C-19 plug. The 208 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13 receptacles. A second PDU (E7672A) is available, which can be daisychained to the 16-amp unit, providing ten more C-13 receptacles. The fan (not required if perforated doors--or no doors--are used front and back) plugs into one of the C-13 receptacles on the PDU. 29