HP Latex 3600 Site Preparation Guide - Page 11

Power distribution unit (PDU), Power specifications

Page 11 highlights

NOTE: The HP Internal Print Server power can be obtained by making a connection inside the electrical cabinet. 2. Power Distribution Unit (PDU) including single-phase branch circuit breaker (optional) 3. Power Distribution Unit (PDU) including three-phase or two-phase branch circuit breaker depending on the power configuration NOTE: Remember that you are required to follow the local laws, regulations, and standards that apply to the electrical installation of your printer. NOTE: The printer is not supplied with any power cable. Power distribution unit (PDU) The PDU must be rated to meet the power requirements of the printer, and should be in accordance with the Electrical Code requirements of the local jurisdiction of the country where the equipment is installed. Power specifications NOTE: If you purchased a Jumbo Roll Solution, check electrical specifications. See Additional electrical configuration for the jumbo roll units on page 11. Configuration 1: 380-415 V line-to-line three-phase configuration Table 2-2 Three-phase specifications Number of power wires 5 (L1/L2/L3/N/PE) Input voltage (line-to-line) 380-415 V~ (±10%) Input frequency 50/60 Hz Power consumption (typical) 9-11 kW Maximum load current (per phase) 35 A Table 2-3 Branch circuit breaker specifications Three-phase 4 poles, 40/50 A Table 2-4 AC three-phase power cable specifications Configuration 5 wires, L1/L2/L3/N/PE Wire Strained Cu minimum, 10 mm² or 8 AWG Terminals Lines, ferrule terminals, PE, M8 ring terminal External diameter range 22.0-33.0 mm ENWW System operation requirements 7

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39

NOTE:
The HP Internal Print Server power can be obtained by making a connection inside the electrical
cabinet.
2.
Power Distribution Unit (PDU) including single-phase branch circuit breaker (optional)
3.
Power Distribution Unit (PDU) including three-phase or two-phase branch circuit breaker depending on the
power configuration
NOTE:
Remember that you are required to follow the local laws, regulations, and standards that apply to the
electrical installation of your printer.
NOTE:
The printer is not supplied with any power cable.
Power distribution unit (PDU)
The PDU must be rated to meet the power requirements of the printer, and should be in accordance with the
Electrical Code requirements of the local jurisdiction of the country where the equipment is installed.
Power specifications
NOTE:
If you purchased a Jumbo Roll Solution, check electrical specifications. See
Additional electrical
configuration
for the jumbo roll units
on page
11
.
Configuration 1: 380–415 V line-to-line three-phase configuration
Table 2-2
Three-phase specifications
Number of power wires
5 (L1/L2/L3/N/PE)
Input voltage (line-to-line)
380–415 V~ (±10%)
Input frequency
50/60 Hz
Power consumption (typical)
9–11 kW
Maximum load current (per phase)
35 A
Table 2-3
Branch circuit breaker specifications
Three-phase
4 poles, 40/50 A
Table 2-4
AC three-phase power cable specifications
Configuration
5 wires, L1/L2/L3/N/PE
Wire
Strained Cu minimum, 10 mm² or 8 AWG
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
External diameter range
22.0–33.0 mm
ENWW
System operation requirements
7