HP Latex 3600 Site Preparation Guide - Page 14

Configuration 6: 240 V line-to-line single-phase configuration with single-phase control

Page 14 highlights

Table 2-15 Branch circuit breaker specifications Two-phase 2 poles, 90 A Table 2-16 AC single-phase power cable specifications Configuration 3 wires, L1/L2/PE Wire Strained Cu minimum, 4 AWG Terminals Lines, ferrule terminals, PE, M8 ring terminal External diameter range 22.0-33.0 mm Configuration 6: 240 V line-to-line single-phase configuration with single-phase control NOTE: Three-phase power provides a more efficient means of supplying large electrical loads than singlephase power, which is common in offices and homes. Connect single-phase if no three-phase power is available. Table 2-17 Specifications Number of power wires Input voltage (line-to-line) Input frequency Power consumption (typical) Maximum load current (per phase) Two-phase line 3 (L1/L2/ PE) 240 V (±10%) 50/60 Hz 9-11 kW 72 A Single-phase control 3 (L/N/PE) 100-240 V (±10%) 50/60 Hz 0.5 kW 10 A Table 2-18 Branch circuit breaker specifications Two-phase line 2 poles, 90 A Two-phase control 2 poles, 15/16/20 A Table 2-19 AC power cable specifications Two-phase line Single-phase control Configuration 3 wires, L1/L2/ PE 3 wires, L/N/PE Wire Strained Cu minimum, 4 AWG Strained Cu minimum, 1.5 mm² or 16 AWG Terminals Lines, ferrule terminals, PE, M8 ring terminal Lines, ferrule terminals, PE, M4 ring terminal External diameter range 22.0-33.0 mm 5.0-11.0 mm If your facilities do not provide the required AC 400VAC line-to-line voltage additional transformer equipment may be needed. 10 Chapter 2 Site preparation ENWW

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39

Table 2-15
Branch circuit breaker specifications
Two-phase
2 poles, 90 A
Table 2-16
AC single-phase power cable specifications
Configuration
3 wires, L1/L2/PE
Wire
Strained Cu minimum, 4 AWG
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
External diameter range
22.0–33.0 mm
Configuration 6: 240 V line-to-line single-phase configuration with single-phase control
NOTE:
Three-phase power provides a more efficient means of supplying large electrical loads than single-
phase power, which is common in offices and homes. Connect single-phase if no three-phase power is available.
Table 2-17
Specifications
Two-phase line
Single-phase control
Number of power wires
3 (L1/L2/ PE)
3 (L/N/PE)
Input voltage (line-to-line)
240 V (±10%)
100–240 V (±10%)
Input frequency
50/60 Hz
50/60 Hz
Power consumption (typical)
9–11 kW
0.5 kW
Maximum load current (per phase)
72 A
10 A
Table 2-18
Branch circuit breaker specifications
Two-phase line
2 poles, 90 A
Two-phase control
2 poles, 15/16/20 A
Table 2-19
AC power cable specifications
Two-phase line
Single-phase control
Configuration
3 wires, L1/L2/ PE
3 wires, L/N/PE
Wire
Strained Cu minimum, 4 AWG
Strained Cu minimum, 1.5 mm² or 16 AWG
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
Lines, ferrule terminals, PE, M4 ring terminal
External diameter range
22.0–33.0 mm
5.0–11.0 mm
If your facilities do not provide the required AC 400VAC line-to-line voltage additional transformer equipment
may be needed.
10
Chapter 2
Site preparation
ENWW