Configuration 4: 200–240 V line-to-line three-phase configuration with single-phase control

Page 13 highlights

Table 2-10 AC Power cable specifications (continued) Three-phase line Single-phase line Terminals Lines, ferrule terminals, PE, M8 ring terminal Lines, ferrule terminals, PE, M4 ring terminal External diameter range 22.0-33.0 mm 5.0-11.0 mm Configuration 4: 200-240 V line-to-line three-phase configuration with single-phase control Table 2-11 Specifications Three-phase line Single-phase control Number of power wires Input voltage (line-to-line) Input frequency Power consumption (typical) Maximum load current (per phase) 4 (L1/L2/L3/PE) 200-240 V (±10%) 50/60 Hz 9-11 kW 56 A 3 (L/N/PE) 100-240 V (±10%) 50/60 Hz 0.5 kW 10 A Table 2-12 Branch circuit breaker specifications Three-phase 3 poles, 63/70 A Two-phase control 2 poles, 15/16/20 A Table 2-13 AC Power cable specifications Three-phase line Single-phase line Configuration 4 wires, L1/L2/L3/PE 3 wires, L/N/PE Wire Strained Cu minimum, 10 mm² or 6 AWG Strained Cu minimum, 2.5 mm² or 16 AWG Terminals Lines, ferrule terminals, PE, M8 ring terminal Lines, ferrule terminals, PE, M4 ring terminal External diameter range 22.0-33.0 mm 5.0-11.0 mm Configuration 5: 240 V line-to-line single-phase configuration NOTE: Three-phase power provides a more efficient means of supplying large electrical loads than singlephase power, which is common in offices and homes. Connect single-phase if no three-phase power is available. Table 2-14 Single-phase specifications Number of power wires 3 (L1/L2/PE) Input voltage (line-to-line) 240 V (±10%) Input frequency 50/60 Hz Power consumption (typical) 9-11 kW Maximum load current (per phase) 72 A ENWW System operation requirements 9

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39

Table 2-10
AC Power cable specifications (continued)
Three-phase line
Single-phase line
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
Lines, ferrule terminals, PE, M4 ring terminal
External diameter range
22.0–33.0 mm
5.0–11.0 mm
Configuration 4: 200–240 V line-to-line three-phase configuration with single-phase control
Table 2-11
Specifications
Three-phase line
Single-phase control
Number of power wires
4 (L1/L2/L3/PE)
3 (L/N/PE)
Input voltage (line-to-line)
200–240 V (±10%)
100–240 V (±10%)
Input frequency
50/60 Hz
50/60 Hz
Power consumption (typical)
9–11 kW
0.5 kW
Maximum load current (per phase)
56 A
10 A
Table 2-12
Branch circuit breaker specifications
Three-phase
3 poles, 63/70 A
Two-phase control
2 poles, 15/16/20 A
Table 2-13
AC Power cable specifications
Three-phase line
Single-phase line
Configuration
4 wires, L1/L2/L3/PE
3 wires, L/N/PE
Wire
Strained Cu minimum, 10 mm² or 6 AWG
Strained Cu minimum, 2.5 mm² or 16 AWG
Terminals
Lines, ferrule terminals, PE, M8 ring terminal
Lines, ferrule terminals, PE, M4 ring terminal
External diameter range
22.0–33.0 mm
5.0–11.0 mm
Configuration 5: 240 V line-to-line single-phase configuration
NOTE:
Three-phase power provides a more efficient means of supplying large electrical loads than single-
phase power, which is common in offices and homes. Connect single-phase if no three-phase power is available.
Table 2-14
Single-phase specifications
Number of power wires
3 (L1/L2/PE)
Input voltage (line-to-line)
240 V (±10%)
Input frequency
50/60 Hz
Power consumption (typical)
9–11 kW
Maximum load current (per phase)
72 A