HP R1500 HP UPS R5000 Installation Instructions - Page 7

Connecting the USB communications port, Connecting the REPO port, Connecting the ground bonding cable

Page 7 highlights

Connecting the USB communications port NOTE: This port is only used for firmware upgrades. For additional information, see the HP UPS R5000 User Guide. • Use tie wraps and tie wrap blocks to secure the wires tightly to the rack and the rear of the UPS. Connecting the REPO port WARNING: The pins on the REPO port are polarity sensitive. Be sure to verify polarity while connecting the REPO port. WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a UPS installed in a computer equipment room must be connected to a REPO circuit. IMPORTANT: The remote switch must be in the Off (open) position to enable power to the output receptacles. For more information about the REPO port, see "REPO port" in the user guide. For information about verifying the REPO connection, see "Verifying the REPO port connection" in the user guide. Connecting the ground bonding cable The ground bonding screw is provided as an attachment point for conductors. Use a ground bonding cable if the rack contains any conductors for the purpose of functional grounding or bonding of ungrounded metal parts. The ground bonding cable is not included. NOTE: Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or equivalent). Separate wire pairs are attached to a single, normally-open contact in a parallel connection. HP recommends using different colors for the positive and negative wires. If a connector becomes disconnected and is reconnected with reversed polarity, a REPO is initiated. To avoid REPO port disconnect: • Minimize wire strain while connecting the REPO port. • Avoid allowing the wires to hang in the rear of the UPS.

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11

Connecting the USB communications port
NOTE:
This port is only used for firmware upgrades. For
additional information, see the
HP UPS R5000 User Guide
.
Connecting the REPO port
WARNING:
The pins on the REPO port are polarity
sensitive. Be sure to verify polarity while connecting the
REPO port.
WARNING:
To meet the requirements stated in NEC
(NFPA 70) Articles 645-10 and 645-11, a UPS installed in
a computer equipment room must be connected to a REPO
circuit.
IMPORTANT:
The remote switch must be in the Off (open)
position to enable power to the output receptacles.
NOTE:
Wire the connector block using stranded,
nonshielded wire (AWG #22 - #18, or equivalent).
Separate wire pairs are attached to a single, normally-open contact in
a parallel connection. HP recommends using different colors for the
positive and negative wires.
If a connector becomes disconnected and is reconnected with reversed
polarity, a REPO is initiated. To avoid REPO port disconnect:
Minimize wire strain while connecting the REPO port.
Avoid allowing the wires to hang in the rear of the UPS.
Use tie wraps and tie wrap blocks to secure the wires tightly to the
rack and the rear of the UPS.
For more information about the REPO port, see "REPO port" in the user
guide.
For information about verifying the REPO connection, see "Verifying
the REPO port connection" in the user guide.
Connecting the ground bonding cable
The ground bonding screw is provided as an attachment point for
conductors. Use a ground bonding cable if the rack contains any
conductors for the purpose of functional grounding or bonding of
ungrounded metal parts.
The ground bonding cable is not included.